Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMPIUDC TEST:(contilnued) <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: INCON STS <br /> SUMP/UDC ID UDC 9110 UDC 11112 <br /> Sump Manufacturer Bravo Bravo <br /> Sump Depth (inches) 32 32 <br /> Sump Bottom to Top of 10 10 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 11:50 11:50 <br /> Initial Reading 3.7098 6.5254 <br /> Test End Time 12:05 12:05 <br /> Final Reading 3.7102 6.5260 <br /> Change in Reading 0.0004 0.0006 <br /> Pass/Fail Criteria 0.002 0.002 <br /> Tightness Test Results ® Pass ❑ Fall ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump1UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />