Laserfiche WebLink
im6ETTLER-RYAN INC. FORM 1 GR Job # 22100032.1 <br /> SUMMARY OF SOURCE TEST DATA <br /> SOURCE INFORMATION FACILITY PARAMETERS <br /> GDF Name and Address GDF Representative and Title PHASE II SYSTEM TYPE <br /> Arco 2093 Vince Caluag (Check One) <br /> 3425 Tracy Blvd. <br /> Tracy, CA 95376 GDF Phone No Balance <br /> 916-858-9907 Hirt <br /> Permit Condltlons Source,GDF Vapor Recovery System Red Jacket <br /> CAS Hasstech <br /> Healy <br /> GDF# Other <br /> A/C# Manifolded7 Yes NO <br /> Operating Parameters <br /> Number of Nozzles Served by Tank#1 8 Number of Nozzles Served by Tank#3 8 <br /> Number of Nozzles Served by Tank#2 8 Number of Nozzles Served by Tank#4 8 <br /> Applicable Regulations: VR-203-1 and VR-204.1 VN Recommended <br /> Source Test Results and Comments <br /> Tank#: 1 2 3 4 <br /> 1. Product Grade 87 87 87 91 <br /> 2. Actual Tank Capacity,gallons 9684 9684 9684 9684 <br /> 3. Gasoline Volume Total 4921 4896 5030 3912 <br /> 4. Ullage,gallons(#2-#3) 19977 4763 4788 4654 5772 <br /> 5. Initial Pressure, inches H2O 2.00 <br /> 6. Pressure After 1 Minute, inches H2O 2.01 <br /> 7. Pressure After 2 Minutes, inches H2O 2.03 <br /> 8. Pressure After 3 Minutes, inches H2O 2.02 <br /> 9. Pressure After Minutes, inches H2O 2.02 <br /> 10. Final Pressure After 5 Minutes,inches H2O 2.04 <br /> 11. Allowable Final Pressure 1.93 <br /> Test Conducted by: Test Company: Date of Test: <br /> Robert Jacobs Gettler-Ryan Inc. 7/8/2022 <br /> California Air Resource Board March 17, 1999 <br /> TP-201.3, Page 14 <br />