Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-PS-87 2-PS-91 3-PS-Diesel UDC 1&2 <br /> Sump Manufacturer Western FG Western FG Western FG Bravo <br /> Sump Depth (inches) 56" 59" 56" 8" <br /> Sump Bottom to Top of 15" 25" 19" BP <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:22 9:27 10:12 9:32 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 9:52 9:57 10:42 10:02 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results M Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail N Pass ❑ Fail <br /> Sump/UDC ID UDC 3&4 UDC 5&6 UDC 7&8 UDC 9&10 <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 8" 8" 8" 8" <br /> Sump Bottom to Top of BP BP BP BP <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:37 10:17 10:22 10:27 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 10:07 10:47 10:52 10:57 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />