Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer D Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used: Incon Tester <br /> Sump/UDC ID 87 STP 91 STP 87 FS 91 FS <br /> Sump Manufacturer Fiberglass Fiberglass Fiberglass Fiberglass <br /> Sump Depth (inches) 68" 68" 68" 68" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 26" 26" 24" 24" <br /> (inches) <br /> Test Start Time 10:34 am 10:54 am 9:48 am 9:28 am <br /> Initial Reading 3.9110 4.1044 4.5152 4.2122 <br /> Test End Time 10:49 am 11:09 am 10:03 am 9:43 am <br /> Final Reading 3.8671 4.1051 4.5145 4.2115 <br /> Change in Reading 0.0439 0.0007 0.0007 0.0007 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results ❑ Pass 0 Fail 0 Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail <br /> Sump/UDC ID UDC 1/2 UDC 3/4 UDC 5/6 UDC 7/8 <br /> Sump Manufacturer Environ oPw oPw oPw <br /> Sump Depth (inches) 31" 31" 31" 31" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 18" 18" 18" 18.. <br /> (inches) <br /> Test Start Time N/A N/A 2:47 pm 12:58 pm <br /> Initial Reading N/A N/A 2.7750 6.1913 <br /> Test End Time N/A N/A 3:02 pm 1:13 pm <br /> Final Reading N/A N/A 2.7736 6.1908 <br /> Change in Reading N/A N/A 0.0014 0.0005 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results ❑ Pass 0 Fail ❑ Pass El Fail 0 Pass ❑ Fail 0 Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />