ELECTRICAL GENERAL NOTES <br /> ANY EXISTING FIRE ALARM SYSTEM SHALL REMAIN IN OPERATION THROUGHOUT <br /> A. ANY EXISTING CONDITIONS INDICATED IN THIS SET OF DRAWINGS ARE BASED ON F. CONSTRUCTION.AUTOMATIC SMOKE DETECTORS IN THE AREA OF CONSTRUCTION <br /> INFORMATION PROVIDED BY OTHERS AND POSSIBLE LIMITED FIELD VERIFICATION. SHALL BE DISCONNECTED AND TEMPORARILY REPLACED WITH HEAT DETECTORS WHEN <br /> THE CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD CONDITIONS AT NO THE SPACE IS STAFFED BY THE CONTRACTOR IN ACCORDANCE WITH THE APPROVED <br /> ADDITIONAL EXPENSE TO THE OWNER. FIRE SAFETY PROCEDURES OF THE OWNER AND THE LOCAL FIRE MARSHALL, BUT Zr <br /> B. THE CONTRACTOR SHALL VISIT THE PROJECT SITE, REVIEW EXISTING CONDITIONS SHALL BE REACTIVATED WHENEVER THE SPACE IS NOT OCCUPIED BY THECONTRACTOR.AUTOMATIC SMOKE DETECTORS SHALL BE PROTECTED FROM DUST AND <br /> AGAINST THE CONTRACT DOCUMENTS,AND FAMILIARIZE HIMSELF WITH THE WORK <br /> PRIOR TO BIDDING AND START OF THE WORK. BY SIGNING THE CONTRACT,THE DIRT ACCUMULATION BY REMOVING THE DEVICE FROM ITS BASE DURING THOSETIMES WHEN THE SYSTEM IS ALLOWED TO BE OUT OF OPERATION. <br /> CONTRACTOR ACKNOWLEDGES THE SITE VISIT HAS BEEN COMPLETED AND THE <br /> EXISTING CONDITIONS ARE ACCEPTED. G. WHERE THE MECHANICAL DESIGN UTILIZES A PLENUM RETURN AIR CEILING <br /> C. THE CONTRACTOR IS RESPONSIBLE FOR DEMOLITION OF EXISTING EQUIPMENT, DESIGN,ALL EQUIPMENT AND MATERIALS INSTALLED WITHIN THE PLENUM RETURN <br /> DEVICES, LUMINAIRES, CONDUITS, SUPPORTS, HANGERS, ETC.THAT ARE NOT CEILING MUST MEET THE FLAME SPREAD AND SMOKE DEVELOPED RATINGS OF 25/50 <br /> SHOWN AND ARE REQUIRED TO BE REMOVED IN ORDER TO COMPLETE THE NEW AND BE APPROVED FOR USE IN PLENUM RETURN CEILINGS. COORDINATE PLENUM <br /> WORK. CEILING LOCATIONS WITH THE MECHANICAL CONTRACTOR. LUMINAIRES THAT ARE I <br /> ©2017 STARBUCKS COFFEE COMPANY <br /> MANUFACTURED WITH A METAL HOUSING MEET THIS REQUIREMENTAND ARE NOT <br /> D. ELECTRICAL CIRCUITS THAT ARE TO BE REMOVED SHALL BE REMOVED IN THEIR REQUIRED TO BE PLENUM RATED UNLESS INDICATED OTHERWISE. <br /> ENTIRETY. CONDUCTORS SHALL BE REMOVED FROM THE ITEM TO BE DEMOLISHED COORDINATE ALL DEVICE LOCATIONS AND CIRCUIT ROUTING WITHIN ANY MILLWORK STARBUCKS COFFEE <br /> TO THE SOURCE OVERCURRENT DEVICE. RACEWAYS WHICH ARE INSTALLED IN OR WITH MILLWORK VENDOR PRIOR TO ROUGH-IN. <br /> BELOW FLOORS OR WITHIN WALLS MAY BE ABANDONED, BUT ALL OVERHEAD OR H. COORDINATE ALL DEVICE LOCATIONS AND CIRCUIT ROUTING WITH ANY MILLWORK COMPANY <br /> EXPOSED RACEWAYS SHALL BE REMOVED. EXPOSED RACEWAYS TO BE ABANDONED WITH MILLWORK VENDOR PRIOR TO ROUGH-IN. <br /> SHALL BE REMOVED AND SHALL BE CUT OR CHISELED AT LEAST 2"INTO THE WALL 2401 UTAH AVENUE SOUTH <br /> OR FLOOR AND THE OPENING GROUTED SMOOTH. I. COORDINATE THE CONNECTIONS OF ALL EQUIPMENT PROVIDED BY OTHERS WITH THE SEATTLE,WASHINGTON 98134 <br /> E. MAINTAIN CONTINUITY OF EXISTING CIRCUITS AS REQUIRED TO PROVIDE POWER <br /> CONTRACTOR PROVIDING THE EQUIPMENT PRIOR TO ROUGH-IN. THIS INCLUDES, 1 (206)318-1575 TO REMAINING EQUIPMENT, DEVICES,AND LUMINAIRES THAT ARE NOT BEING BUT IS NOT LIMITED TO, MECHANICAL EQUIPMENT, KITCHEN EQUIPMENT, <br /> AUDIOVISUAL EQUIPMENT, FIRE SUPPRESSION SYSTEM EQUIPMENT, FIRE ALARM THESE DRAWINGS AND SPECIFICATIONS ARE <br /> REMOVED. EQUIPMENT, ETC. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE CONFIDENTIAL AND SHALL REMAIN THE SOLE <br /> THE APPROPRIATE DISCONNECTING MEANS FOR,AND TO MAKE THE FINAL PROPERTY OF STARBUCKS CORPORATION, <br /> CONNECTION TO,ANY HARDWIRED EQUIPMENT. THE ELECTRICAL CONTRACTOR IS WHICH IS THE OWNER OF THE COPYRIGHT IN <br /> ALSO RESPONSIBLE TO PROVIDE AN APPROPRIATE CORD AND PLUG FOR ANY THIS WORK. THEY SHALL NOT BE <br /> CORD-AND-PLUG CONNECTED EQUIPMENT THAT IS NOT EQUIPPED WITH AN INTEGRAL <br /> CORD AND PLUG. REPRODUCED (IN WHOLE OR IN PART), SHARED <br /> WITH THIRD PARTIES OR USED IN ANY MANNER <br /> J. SEE PANEL SCHEDULES FOR INFORMATION ON CIRCUITS THAT ARE TO BE ROUTED ON OTHER PROJECTS OR EXTENSIONS TO THIS <br /> THROUGH CONTACTORS OR RELAYS FOR CONTROL. PROJECT WITHOUT THE PRIOR WRITTEN <br /> CONSENT OF STARBUCKS CORPORATION. <br /> K. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PRESERVING THE FIRE RATING THESE DRAWINGS AND SPECIFICATIONS ARE <br /> OF ANY FIRE-RATED CEILING ASSEMBLIES BY PROVIDING THE APPROPRIATE INTENDED TO EXPRESS DESIGN INTENT FORA <br /> FIRE-RATED LUMINAIRE TENTS AS MANUFACTURED BY TENANT OR NELSON FIRESTOP PROTOTYPICAL STARBUCKS STORE(WHICH IS <br /> OR BY BUILDING FIRE-RATED ENCLOSURES AROUND EACH LUMINAIRE THAT IS SUBJECT TO CHANGE AT ANYTIME)AND DO <br /> RECESSED INTO THE FIRE-RATED ASSEMBLY. COORDINATE FIRE-RATED CEILING NOT REFLECT ACTUAL SITE CONDITIONS. <br /> ASSEMBLY LOCATIONS WITH THE ARCHITECTURAL DRAWINGS. NEITHER PARTY SHALL HAVE ANY OBLIGATION <br /> L. ALL EQUIPMENT, DEVICES,AND LUMINAIRES SHALL BE SUITABLE FOR THE NOR LIABILITY TO THE OTHER(EXCEPT STATED <br /> ENVIRONMENT IN WHICH THEY ARE INSTALLED. EQUIPMENT MOUNTED OUTDOORS ABOVE) UNTIL A WRITTEN AGREEMENT IS <br /> SHALL BE NEMA 3R. DEVICES MOUNTED IN DAMP OR WET LOCATIONS SHALL BE FULLY EXECUTED BY BOTH PARTIES. <br /> WEATHERPROOF. RECEPTACLES RATED 15-OR 20-AMPS AND 120 VOLTS WHICH ARE <br /> LOCATED IN DAMP OR WET LOCATIONS SHALL BE GFCI PROTECTED AND EQUIPPED <br /> WITH A SUITABLE WEATHERPROOF COVERPLATE(WHILE-IN-USE IN WET ARCHITECT OF RECORD <br /> LOCATIONS). mcg architecture <br /> M. ALL LUGS, TERMINALS, ETC. IN ELECTRICAL DISTRIBUTION EQUIPMENT SHALL BE � 0� m <br /> LISTED FOR A MINIMUM OF 75 DEGREE C CONDUCTORS. TERMINATIONS LISTED �U G1 <br /> 5 '_ <br /> >- - <br /> FOR ONLY 60 DEGREE C CONDUCTORS ARE NOT PERMITTED. � o <br /> U <br /> N. BRANCH CIRCUITS RATED AT 20 AMPS AT 120 VOLTS THAT ARE LONGER THAN 75 Cz <br /> -- -- -- --- cn <br /> FEET SHALL BE#10 AWG MINIMUM TO OFFSET VOLTAGE DROP. <br /> . <br /> _____.I _____ 15635 Alton Parkway Suite 100 Irvine CA 92618 <br /> O. BRANCH CIRCUITS RATED AT 20 AMPS AT 120 VOLTS THAT ARE LONGER THAN 150 <br /> .. *2 FEET SHALL BE#8 AWG MINIMUM TO OFFSET VOLTAGE DROP. P. 949.553.1117 F:949.474.7056 <br /> . I I )* <br /> A 10010 A 12336 *2 <br /> A 10012 A 14677 P. BRANCH CIRCUITS RATED AT 20 AMPS AT 277 VOLTAS THAT ARE LONGER THAN 150 PROFESSIONAL STAMP <br /> +22 44 ___ FEES SHALL BE#10 AWG MINIMUM TO OFFSET VOLTAGE DROP. Qpof Ess ioN <br /> A 10014 A 14678 o OY q/ <br /> +22 42 Q. CONDUCTORS#12 AWG AND SMALLER SHALL BE SOLID.CONDUCTORS#10 AWG AND ��q- off, R Sch� �I <br /> LARGER ARE PERMITED TO BE STRANDED. 9� <br /> *2 *2 *2 - rn z <br /> Q A-52,54 D A-40,42,44 C' N E146 <br /> 54 3 40 ELECTRICAL PLAN NOTES <br /> 5 <br /> 54 3g 35 0ALL RECEPTACLES IN THIS AREA SHALL HAVE FACEPLATE GFCI PROTECTION. m� F�ECTR ICP' ��P <br /> kn TF o� <br /> r A-35,37,39 0 F <br /> ........ ......... ......... ......... ......... ......... ......... ......... ......... ......... ......... ......... ......... ......... ......... ......... ......... _._. ..(D cD _ ___..... ____..... ____..... ____..... ____..... ____..... ____..... ____..... ____..... ____..... ____..... ____ ____..... ____..... ____..... ____..... ____..... ____..... ____..... ____..... ____..... ____..... ____..... ____..... F <br /> ­iiiiiiiiiiiiiiiii., <br /> . <br /> �I1.Ii..'.�I1'''I'III..'.�I1I.�.�II..�II.IIII................................... <br /> �I.�I.�I.�I�. <br /> .�I.�I.�I.�I.�I.�I.�I.�I.�I.�I7.�I..�I. <br /> ''�- <br /> em <br /> II <br /> 02<F_-_3 0000>3z.I1W..s..s.— <br /> .6...).).- <br /> :::] <br /> 00 C A <br /> 52 + *2 A-53, 2O PROVIDE ONE 2 EMT CONDUIT WITH PULL STRING FROM EXISTING TELEPHONE <br /> D W/RE E 20032 (2) DEMARCATION FOR TELEPHONE SERVICE. FIELD VERIFY EXACT LOCATION <br /> (#8 <br /> Date. 02 23 2021 <br /> TING TELEPHONE POINT OF CONNECTION AND CONDUIT ROUTING PRIOR TO <br /> / / <br /> E 19559 E 10267 <br /> (2)E 12508 38 6-30R 6-30R 41�II.�II.*�I..........................................I-:...........IIIIIIIIIII I.1�I.I.1�I.I.1.�I........................................-:......I.1..�I.­:......�I..�I­.­..II....................................II1�I�I1...­..I.�I11­.1....I.�I1­11.:1.....I.�I11­.1.....�I1­117.....�I11­.1....,.�I.­1I.1.....,1.�1.­.-..110..,... <br /> �1..1I...,.�1­.1I..,.�I1.1I.-......,.�I.II.,.�I.II.,.�I.II.,.�I.II.,.�I.II..I.�I..I..I.�I�.I.I.�I".I.rI.�I..I.I.�I".I.I.i�I..I."I.�I.I..I.�I..I.I.�I­.II.I.�I..II.I. <br /> 37 35 5-20R BID. <br /> 36 34 E 20010 37 <br /> �.���I.�I11..�I11..—�I11.�I11�I1�I.�I.�I.�I.�II­.�..I11.�-.I1.�.III.�II.�II.:�II.�II.�II.�II.�II.�I.:�I.�I.�I.�I.�I.--�I.�I.�II.�II.�II.�II.�II.�II.�II.�II.�1. <br /> ...1.I:.II.�1II1.I.....:­..Ifi.......1.I111111:II.i",11II1.I.,.:..I......I,:.II.,.­11II1I..:­..I..1.I,:II."IIIII....I...-..I,..II.J1II.I..11..I....,.I,.II.,.-1II-­I....I.­.....I,­II.,­.1II.I....I.......I,II.,.­.1II1I..­..I.­...,.I111111,II.,1I1II1I....I..-.....I111111­II.,.­11II.I.-....I.­....­.I,1II.,1-1II.I...­..I......1.I,1II.,.­11II­1I..'...I.­"...,.I,i!1.II/,1IIII.....II..'....,.II1II­-­I.­.1II-II.....I..­......II1III11II.I.....I-­...:...................:IIIIIIIIIIIIIIIIIIII..II1.II­I.11II.I.....I........II1.I/I..1II.I.....I.­....,..I1.I F...­,­1IIIIIIIIIIIIII.."III1II-....I.,...I1.1.....1I1.1.....,.­II.:1.....,..II.,..1..I. <br /> �1,...I1..II.�,...I..II.�,...I-..II.�,...I-..II.�,...I..II.�,,...I...II.�.,...I1..II.�1,...I#...I.�1III"...�III....�III".1111.....�.I.I.1111...I..1.�.II..I-1...1.�II..I1...1.�,1......IIIII..I.....1.�.III..I.I'1111....I...1.�1III..I1....1.�,III..I1.'1111....I....1.�.1,III..I.......1.�.1,III..I......I1.�.1,III..I......I1.�.1,III..I.1.....II.�.1,III..I......II.�.1,III..I.......II.�II.1,III..I <br /> 3.�I.�IA.�I.�I.�I.�I.�I..�.I.I.�.I..�.I <br /> 1.1.1.1..... ......... ......... ......... ......... ......... ........ .. ....... .... ......... ......... ......... .1.1.1.1 .. ......... ......... ......... . .......... <br /> . A 4'-0"x 8'-0"x 3/4" U L <br /> - - <br /> 0 �0 �a 3 PROVIDE LABELED FIRE RETARDANT PLYWOOD <br /> ... ... . <br /> ......... ............... ......... 20 BACKBOARD FOR TELECOMMUNICATIONS EQUIPMENT. PROVIDE GROUND BAR <br /> .. 22 20 <br /> . ... .... <br /> 31 24 <br /> 34 33 29 MOUNTED ON BACKBOARD WITH EQUIPMENT GROUNDING CONDUCTOR <br /> 6-50R CONNECTED TO POWER SYSTEM'S GROUNDING ELECTRODE SYSTEM. SEE <br /> - • <br /> DETAIL 2/E 6001 FOR ADDITIONAL INFORMATION REGARDING GROUND BAR. <br /> A-29,31,33, _ <br /> A-34,36,38 - 0 <br /> �'�/ <br /> I..L <br /> .:: <br /> ........ .. fl 14075 <br /> .. ... <br /> ... ... <br /> .. W <br /> (2}E 10267 (2) E 12618 B 35,37,41, <br /> A—20,22,24, (#12,#6,#12) U' <br /> 12, 1 <br /> E 17564 (# 2,#8) <br /> 2,#8) <br /> .. <br /> .. <br /> W <br /> . . <br /> Z <br /> COQ <br /> w U <br /> . . <br /> o <br /> 3 Q D <br /> E 10267 ( ) <br /> Z <br /> . <br /> ..::::: ::::: <br /> E 10267 E 10808 —41,43, MOULTED TO 1 <br /> A W <br /> .................. .................. ...............: .................. .................. .................. ........................... <br /> 12, <br /> N 00 <br /> - - -- - - - - - - - - # #6 BU OLES <br /> . :: <br /> . O _ O <br /> —2 2 <br /> A 8303 TYP. <br /> A-2125 27 ) A-13,15,17 Q <br /> _ CC <br /> A-474951 .. A 46,48,50 a- 0- ' G <br /> (#8,#12,#12) <br /> �� <br /> 3 SLEEVES <br /> . . ... <br /> . <br /> . . <br /> yi <br /> . . .. <br /> . . . � <br /> '"; <br /> . <br /> ---------- <br /> N <br /> ............................. <br /> 2 2 '2 <br /> N <br /> TORE 24 <br /> . . 48 S O # 65 6 <br /> 6 5 <br /> vvv <br /> . . ... . <br /> OR r 28 ao <br /> . <br /> ... <br /> N <br /> N Cfl + <br /> 49 51 {, ( _ <br /> v' 7 - + N PROJ ECT#: 88584 001 <br /> 51 41 ...- <br /> t1t5Ett4 E I € �4 <br /> i <br /> 48 <br /> rn <br /> 27 rn <br /> 15,. <br /> .: i t 1111 r. <br /> v vv <br /> A—2,6,8, <br /> 6 50R 6 5: R 6 50R cD <br /> 0 cD <br /> * * * PROFILE TYPE: CORE <br /> . 46 <br /> . <br /> 2 2 <br /> . 12 <br /> 6 43 + <br /> 2 <br /> 50 5-20R 30 ISSUE DATE: <br /> 32 <br /> R <br /> 47 <br /> 8 <br /> 25 21 <br /> PROGRAM MANAGE : <br /> A 10075 E 10746 <br /> 2 <br /> ....... ....... ...... A_10014 . . .... ........ ........ .......... .1.1.1.1. ....... ........ <br /> ............... ............... ............... <br /> STOR DESIGNER J RAMOS <br /> A 10014 (3} p 15749 E 19742 (2) E 10312 (2) <br /> A 10008 1317 3 LEEDS AP: N/A <br /> A 10075 (3} A 10014 E 10856 (4) CHECKED BY: GRS <br /> MCG PROJECT#: 20009 <br /> ------------------- --- MCG PR J. MANAGER: C.LEE <br /> MCG PR J. SPECIALIST: S. PARK <br /> ENLARGED MANAGER'S DESK POWER AND <br /> SYSTEMS PLAN Revision Schedule <br /> . 2 N Rev Date By Description <br /> Scale: 1/2"= 1'-0" <br /> SHEET TITLE: <br /> ENLARGED ENGINE <br /> POWER / SYSTEMS PLAN <br /> SCALE:AS SHOWN <br /> II <br /> �NLARGED ENGINE POWER AND SYSTEMS PLAN Schnackel SHEET NUMBER:1 le: 1/2"= 1'-0" N • <br /> ,, E-1102 <br /> BE JOBIk 200472 <br />