Laserfiche WebLink
SAN J 0 A Q I I I Irl Environmental Health Department <br /> CCUNr <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> STOCKTON FOOD&GAS#2 2057 S EL DORADO ST, STOCKTON June 29, 2022 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 306 HSC 25291(e) Failure to remove, analyze, and properly dispose of water in secondary containment(pre-Jul 2003). <br /> OBSERVATION: Liquid was observed in the 87 STP Sump <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it <br /> must be removed and disposed of properly. <br /> CORRECTIVE ACTION: The service technician removed the liquid from the 87 STP sump. Ensure that all sumps <br /> and annular spaces are maintained free of liquid. <br /> This is a Class II violation. <br /> 2010 OBSERVATION: There was a change in ownership that was effective on 9/1/2021.A permit transfer has not been <br /> completed with the EHD and all required elements were not submitted in CERS within 30 days of the change in <br /> ownership. <br /> REGULATION GUIDANCE: Permits may be transferred to new underground storage tank owners if: <br /> 1)the new UST owner does not change conditions of the permit; and <br /> 2)the transfer is reported to the local agency by submitting all of the required submittal elements in CERS within 30 <br /> days of <br /> the change in ownership <br /> CORRECTIVE ACTION: Submit all necessary items to the EHD and provide a corrective action statement. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> An inspection checklist was provided to the facility operator on the day of inspection. A complete report was <br /> finished on 8/30/2022 and replaces the initial checklist. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, within 30 days of receiving the complete inspection report. <br /> NOTE: The monitoring site map incorrectly lists the 87 gasoline tank as having a capacity of 10,000-gallons. <br /> The 87 tank has a capacity of 15,000-gallons. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: August 30, 2022 Inspector: Inspector Phone: <br /> Printed Name and Title: GABRIELA GARCIA-MEJIA, EH Specialist (209)616-3037 <br /> Emailed to Haten Mohammed, Owner <br /> FA0003735 PR0231083 SCO01 06/29/2022 <br /> EHD 23-01 Rev.9/16/2020 Page 8 of 8 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />