A NJ O A Q U l N Environmental Health Department <br /> COUNTY— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: FMa <br /> TRACY 76 2420 W GRANT LINE RD,Tracy 16, 2022 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 205 CCR 2712(i) Failure to have current UST Monitoring Plan readily accessible at the facility. <br /> OBSERVATION:An approved copy of the monitoring plans were not available for inspection. <br /> REGULATION GUIDANCE:A copy of these plans shall be accessible on site at all times. <br /> CORRECTIVE ACTION: Immediately locate and retain a copy on site. <br /> This is a repeat violation, Class Il. <br /> 206 CCR 2712(i), 2634(e)Failure to have a current UST Response Plan available on site. <br /> OBSERVATION:An approved copy of the response plan was not available for inspection. <br /> REGULATION GUIDANCE:A copy of this plan shall be accessible on site at all times. <br /> CORRECTIVE ACTION: Immediately locate and retain a copy on site. <br /> This is a minor violation. <br /> 208 CCR 2716(a-e) Failure to comply with the designated operator inspection requirements. <br /> OBSERVATION: The designated operator failed to check and note the correct test dates for the Overfill Prevention <br /> Equipment on the designated operator inspection reports from October 2021 through March 2022.The correct date <br /> for Overfill Prevention Equipment is 9/27/2021 but was listed as 1/30/2019 on reports from October 2021 through <br /> March 2022. <br /> REGULATION GUIDANCE: During the inspection, the designated operator shall check that all required testing and <br /> maintenance for the UST system have been completed and document the dates they were done. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br /> the required information on the reports. <br /> This is a repeat violation, Class ll. <br /> 317 CCR 2636(f)(2) Failure of the line leak detector to detect a 3.0 gph leak at 10 psi and restrict or shut off flow. <br /> OBSERVATION: The Regular Unleaded (87)VMI line leak detector failed to detect a leak when tested. <br /> REGULATION GUIDANCE:All line leak detectors shall be capable of detecting a 3-gallon per hour leak at 10 psi. <br /> CORRECTIVE ACTION: The service technician adjusted the leak detector, retested it, and it passed.This was <br /> corrected on site. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> FA0003963 PR0231580 SCO01 03/16/2022 <br /> EHD 23-01 Rev.12/06/2021 Page 6 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />