Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer D Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used: Incon Tester <br /> Sump/UDC ID 87 STP 89 STP 91 STP Diesel STP <br /> Sump Manufacturer Fiberglass Fiberglass Fiberglass Fiberglass <br /> Sump Depth (inches) 64" 64" 64" 64" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 25" 24" 25" 25" <br /> (inches) <br /> Test Start Time 9:23 am 9:23 am 9:23 am 10:37 am <br /> Initial Reading 5.3403 6.0611 6.0802 2.4875 <br /> Test End Time 9:38 am 9:38 am 9:38 am 10:52 am <br /> Final Reading 5.3389 6.0599 6.0805 2.4869 <br /> Change in Reading 0.0014 0.0012 0.0003 0.0006 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results p Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail <br /> Sump/UDC ID 87 FILL 89 FILL 91 FILL Diesel FILL <br /> Sump Manufacturer Fiberglass Fiberglass Fiberglass Fiberglass <br /> Sump Depth (inches) 64" 64" 64" 64" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 24" 24" 24" 24" <br /> (inches) <br /> Test Start Time 7:51 am 8:07 am 10:37 am 7:51 am <br /> Initial Reading 4.8039 4.4106 3.8746 3.2873 <br /> Test End Time 8:06 am 8:22 am 10:52 am 8:06 am <br /> Final Reading 4.8035 4.4102 3.8742 3.2870 <br /> Change in Reading 0.0004 0.0004 0.0004 0.0003 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results 0 Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />