Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by ❑ Manufacturer D Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used: Incon Tester <br /> Sump/UDC ID UDC 1/2 UDC 3/4 UDC 5/6 UDC 7/8 <br /> Sump Manufacturer Environ Environ Environ Environ <br /> Sump Depth (inches) 31" 31" 31" 31" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 18" 18" 18" 18" <br /> (inches) <br /> Test Start Time 12:31 pm 10:37 am N/A 11:58 am <br /> Initial Reading 6.1404 5.9745 N/A 4.8569 <br /> Test End Time 12:46 pm 10:52 am N/A 12:14 pm <br /> Final Reading 6.1104 5.7305 N/A 4.8017 <br /> Change in Reading 0.0300 0.2440 N/A 0.0552 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results ❑ Pass 0 Fail ❑ Pass 0 Fail ❑ Pass 0 Fail ❑ Pass 0 Fail <br /> Sump/UDC ID UDC 9/10 UDC 11/12 UDC 13/14 <br /> Sump Manufacturer Environ Environ Environ <br /> Sump Depth (inches) 31" 31" 31" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 181, 18" 181, <br /> (inches) <br /> Test Start Time N/A 11:58 am 11:58 am <br /> Initial Reading N/A 5.3985 4.2559 <br /> Test End Time N/A 12:14 pm 12:14 pm <br /> Final Reading N/A 5.3673 4.2557 <br /> Change in Reading N/A 0.0312 0.0002 <br /> Pass/Fail Criteria 0.002 0.002 0.002 <br /> Tightness Test Results ❑ Pass 0 Fail ❑ Pass El Fail 0 Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />