Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer 2 Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum [0 Hydrostatic <br /> Test Equipment Used: Water / Incon / Probes <br /> Sump/UDC ID UDC 9/10 UDC 11/12 <br /> Sump Manufacturer Western Fiberglass Western Fiberglass <br /> Sump Depth (inches) 30" 30" <br /> Sump Bottom to Top of 16" 16" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 8:24pm 7:48pm <br /> Initial Reading 6.1215 3.7832 <br /> Test End Time 8:39pm 8:03pm <br /> Final Reading 6.1217 3.7830 <br /> Change in Reading 0.0002 -0.0002 <br /> Pass/Fail Criteria +0.002 / -0.002 +0.002 / -0.002 <br /> Tightness Test Results lia Pass ❑ Fail lia Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3of5 <br />