Laserfiche WebLink
LG 162-2 - 6 - <br /> requirements . As with all leak detection equipment used to monitor the UST <br /> system , these methods must be third - party certified and should be listed in Local <br /> Guidance ( LG ) Letter 113 . LG 113 can be found on our website at : <br /> http : //www . waterboards . ca . gov/ust/leak prevention/Ig113/index . html <br /> It is important to note that regulated piping begins where piping exits/enters the <br /> tank and continues to the point where piping extends above the surface of the <br /> ground (e . g . , at a shear valve) . Statute does not provide an exemption for single- <br /> walled piping transitions contained in sumps , or single -walled piping transitions in <br /> UDCs , or fill piping contained in sumps . The following options may be used to <br /> satisfy the requirements for single-walled piping transitions contained in sumps ; <br /> single -walled piping transitions contained in UDCs ; and fill piping contained in <br /> sumps : <br /> i . The entire piping length , including piping within sumps or UDCs , must be <br /> double-walled and continuously monitored using vacuum , pressure , or <br /> interstitial liquid level measurement methods ; or <br /> ii . The interstitial space between the primary ( i . e . , single-walled transition <br /> pipe or fill piping ) and secondary containment ( i . e . , sump , UDC ) must be <br /> continuously monitored using vacuum or pressure . ( Note : Interstitial liquid <br /> level measurement would not be appropriate for this option . ) ; or <br /> iii . The single-walled transition pipe or fill piping must be contained within a <br /> double-walled sump and/or double-walled UDC that either: ( 1 ) extends to <br /> the surface or (2) has a double-walled product tight lid that is continuously <br /> monitored using vacuum , pressure , or interstitial liquid level measurement <br /> methods . The secondary containment (of the sump or UDC , including <br /> penetration fittings ) must be continuously monitored using vacuum , <br /> pressure , or interstitial liquid level measurement methods . <br /> Pursuant to Section 2637 ( a ) (6) of Title 23 , CCR , portions of the UST system <br /> which are continuously monitored using vacuum , pressure , or interstitial liquid <br /> level measurement methods are exempt from periodic secondary containment <br /> testing . Therefore , periodic secondary containment testing is not required for <br /> secondary containment of tank and piping that are continuously monitored using <br /> vacuum , pressure , or interstitial liquid level measurement methods . Please note <br /> that annual certification of the leak detection equipment is still required . <br /> Be What components of USTs installed on or after July 1 , 2004 are required to <br /> be monitored in accordance with H &S Code , Section 25290 . 1 ( d ) ? <br /> Section 25290 . 1 requires that the " underground storage tank system " be <br /> designed and constructed with a continuous monitoring system . Tank and <br /> product piping monitored using constant vacuum , pressure , or interstitial liquid <br /> level measurement methods satisfy this requirement through Section 25290 . 1 (e ) . <br /> However, other parts of the UST system not subject to Section 25290 . 1 (e ) must <br /> California Environmental Protection Agency <br /> Qa Recycled Paper <br />