LIQUID TIGHT FLEX CONDUIT TOKNOCKOUT ON UNIT. FINALCONNECTION TO COIL BY GCCEILING MOUNTED WP JUNCTION BOXWITH THREADED HUBS AND GASKETEDCOVERPLATEPROVIDE CEILING MOUNTED MANUALTWO-POLE SWITCH IN WEATHERPROOFENCLOSURE.COOLER/FREEZER BOX CEILINGCONDUIT AND WIRING TO PANELFURNISHED BY OWNER, INSTALLED BY G.C.CONDUIT AT CEILING PENETRATIONFILLED WITH SEALANTCONDUIT PENETRATIONSEALED WITH SILICONESEALANTCONDUIT AND WIRING TONEXT JUNCTION BOX ONSAME SYSTEMTYPICAL COILNOTE: DO NOT LOCATE WP JUNCTION BOX DIRECTLY IN FRONT OF DISCHARGE FAN, OFFSET TO SIDE.3EVAPORATOR COIL WIRINGN.T.S.2PANELBOARD ELEVATIONN.T.S.INTERIOR
<br />EXTERIOR
<br />TO VEEDER
<br />ROOT
<br />WIRE WAYMC CABLELIGHTINGCONTACTORWIRE WAYEMT CONDUITVFC
<br />CBS
<br />VFCWIRE WAYIRIRIRDBOXPAM
<br />TO SALES
<br />COUNTER
<br />GUTTER LOOPS
<br />TO AIR-VAC
<br />TO DISPENSERS
<br />TO PUMPS
<br />DISPENSER
<br />INTERCOM
<br />TO DISPENSERS
<br />TO DISPENSERS
<br />CANOPY LTS
<br />NEWPNLFCANOPY SIGNS
<br />SITE LTS
<br />GUTTER LOOPS NEWPNLSNEWPNLBNEWPNLANEWPNLLTO E-STOPSWIRE WAYWIRE WAYWIRE WAYDDDDIDIDEMSCP-13 POLE-100ACONTACTORSPD23TO VEEDER
<br />ROOTWIRE WAYTO WIREWAYNEWSWITCHGEAR"MDP"(NEMA 3R)TO UTILITY
<br />TRANSFORMER
<br />CEILINGFLOOR27NEWPNLEVEV CHARGERS
<br />WIRE WAYAA.1B1234BUN DRAWERWASTECIG'SCIG'SITPOTPFEM - CHIPS
<br />MAGNUSHSSMAGNUSHSSMAGNUSHSS14E1.611POWER PLAN1/4" = 1'-0"A-91A-7+24"GFCIA-7+42"GFCIB-128A-7+24"GFCI1211174S-23A-18,206-20B-17A-22,24L6-30B-23,25L6-30B-26L5-20+84"B-3+42"B-6B-7GFCIB-11GFCIA-40,426-20A-17GFCI+42"A-36GFCIA-33,35
<br />6-20
<br />A-19,21
<br />6-20
<br />A-10,12
<br />6-20
<br />A-49A-315B-19,21921SPKB-413B-30,32,343P/60A/NF+96"B-8+24"S-5+36"19B-9+93"20B-9+93"GFCI20B-9+93"B-2S-11S-17S-29S-19S-1S-25S-13S-7L-14L-141515L-4L-165+94"24B-1WP/GFCIL-33+94"24L-3318S-31P/30A/NFNEMA-3RA-4WP/GFCI1616A-4WP/GFCI18(TYP)S
<br />JJJJJJ11L-9+86"B-5+42"S-243L-1+214"JNOTE: MONEY ORDER ANDLOTTO CORDS TO BE RANIN SAME GROMMET.L-7+104"RECESSEDCLOCKOUTLETB-27,296-30E1.63E1.022
<br />2E1.64S-22266NOTE: THERE SHALL BE NORECEPTACLES INSTALLED UNDERTHE LOTTO SCRATCH UP AREA.S-20S-225-15R5-15RS-225-15RCLGMTDA-26,28L6-20A-38CLGMTDCLGMTDA-8+42"15A-23,25L14-50+42"B-36,38L14-50+42"B-40GFCI1515A-17GFCIL-14L-1466A-47+72"GFCI15A-51A-14B-20A-27,29L6-30+42"A-13+42"A-11A-5+42"A-48,506-30+42"A-43,456-20+42"F-21F-27A-7+42"GFCI10E1.62L-10+42"WP, GFCI12S-267A-2+24"A-52,54L6-30+42"B-5+42"JS-30+28"JA-44B-28GFCI151515L-8+24"HBL-479225B-5026B-5026B-5026B-138JB-19,21SB-19,21S
<br />"A""B""S""L""F"19B-9+93"J283L-27+221"J"EV""MDP" (NEMA 3R)E1.65A-46+84"+42"3L-22+221"JA-3B-10+24"A-53+72"GFCIA-55+72"GFCIELECTRICAL NOTES:1.ALL RECEPTACLES SERVED FROM PANEL "S" SHALL BE OF THE ISOLATEDGROUND TYPE. ALL CIRCUITS SHALL CONTAIN A HOT, NEUTRAL, GROUNDAND ISOLATED GROUND CONDUCTOR.2.AMPACITY OF ALL CONDUCTOR SIZES SHOWN ON PLANS IS BASED ON 75°CRATED TERMINATIONS AND CONDUCTOR INSULATION. CONTRACTOR SHALLFIELD VERIFY EQUIPMENT TEMPERATURE RATINGS OF ALL TERMINATIONSAND ADJUST CONDUCTOR SIZES PER NEC 110.14(C)3.ALL WIRING IS COPPER. REFER TO ELECTRICAL SPECIFICATIONS FORFURTHER INFORMATION.4.ALL WALL MOUNTED RECEPTACLES SHALL BE 18" A.F.F ON CENTER.UNLESS NOTED OTHERWISE.5.FURNISH AND INSTALL CORD AND CAP FOR ALL EQUIPMENT CONNECTEDTO NEMA L-14R RECEPTACLE.6.G.C. TO COORDINATE POWER REQUIREMENTS FOR EXTERIOR SIGNAGE.7.THE UNGROUNDED AND GROUNDED CONDUCTORS OF EACH MULTIWIREBRANCH CIRCUIT SHALL BE GROUPED BY WIRE TIES OR SIMILAR MEANS INAT LEAST ONE LOCATION WITHIN THE PANELBOARD OR OTHER POINT OFORIGINATION. REF 2011 NEC (210.4(D))8.EACH MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH A MEANSTHAT WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDEDCONDUCTORS AT THE POINT WHERE THE BRANCH CIRCUITS ORIGINATES.REF 2011 NEC (210.4)9.CONDUITS THAT ARE EXPOSED TO WIDELY DIFFERENT TEMPERATURES,SUCH AS COOLERS, FREEZERS OR SERVICE ENTRANCE CONDUCTORS,SHALL BE SEALED TO PREVENT CIRCULATION OF AIR AND/OR MOISTURE.REF 2011 NEC (300.7 (A))10.CONDUIT AND WIRING IN AREAS WHERE EXPOSED SHALL BE ROUTED AT 90DEGREE ANGLES PERPENDICULAR OR PARALLEL TO JOISTS. COORDINATEPAINTING OF CONDUIT WITH ARCHITECTURAL FINISHES.JSSPECIAL RECEPTACLE(SEE NEMA CONFIG)WALL SWITCHNON-FUSED DISCONNECTJUNCTION BOX125 V RECEPTACLE,DUPLEXTELEPHONE/DATA OUTLETSYMBOL LEGENDPANEL BOARD125 V RECEPTACLE,SIMPLEX125 V RECEPTACLE,DOUBLE DUPLEX125 V RECEPTACLE,CEILING MOUNT DUPLEXWEATHERPROOF SPEAKERFUEL E-STOPFUSED DISCONNECT(NOTE: NOT ALL SYMBOLS ARE USED)KEYNOTES - POWER12DEVICES SHALL BE NEMA 5-20 UNLESS NOTED OTHERWISE. TYP OF120V-20A CIRCUITS.3EXTERIOR SIGNAGE J-BOX. COORDINATE FINAL LOCATION WITHSIGNAGE CONTRACTOR AND CONSTRUCTION MANAGER. RUNEXTERIOR BUILDING SIGNS THROUGH PHOTOCELL DRIVENCONTACTOR. PROVIDE PAD-LOCKABLE BREAKER FOR MAINTENANCE.4ENERGY MANAGEMENT ENCLOSURE PROVIDED BY OTHERS, PROVIDE120V DEDICATED CIRCUIT ONLY.56RECEPTACLE FOR ATM SIGN. VERIFY LOCATION WITH CONSTRUCTIONMANAGER PRIOR TO COMMENCEMENT OF WORK.7WINDOW RECEPTACLES. MOUNT FLUSH IN CEILING, MOUNTABOVE WINDOW HEADER IN OPEN CEILING AREA, PER NEC8910REFER TO EVAPORATOR COIL WIRING DETAIL, RE: 3/E1.0, TYP.1112VEEDER ROOT: COORDINATE INSTALLATION WITH FUELING PLANS.INSTALL IN ACCESSIBLE LOCATION. MOUNT AT 48" A.F.F. TO BOTTOM.13RECEPTACLE FOR MOTION SENSOR FAUCET. REFER TOARCHITECTURAL SHEETS FOR EXACT ROUGH-IN LOCATIONS, TYP.14RECEPTACLE FOR WATER FILTRATION BOOSTER PUMP, E.C. TO INSTALLWATER-RESISTANT, "WHILE-IN-USE" COVER.151617ROUTE CIRCUITRY FOR EQUIPMENT UNDER SLAB, RE: 1/E1.218SERVICE RECEPTACLE, WEATHERPROOF GFCI.19REFER TO DETAIL #5 ON GAS PLANS SHEET G10 FOR PANEL 'F' CONDUITROUTING.20EMERGENCY GAS SHUT-OFF @ 48" A.F.F.21TRANSMITTER RECEPTACLE, G.C. TO PROVIDE. MR. CHIME ENTRANCEALERT TRANSMITTER (DA4TAC). CONTACT MR. CHIME AT 877-672-4463.RECEIVER RECEPTACLE, G.C. TO PROVIDE. MR. CHIME RECEIVER (DARD).INSTALL WEATHERPROOF SPEAKER, G.C. TO PROVIDE MR. CHIMESPEAKER (SPK).MOUNT ON WALL IN WALK IN COOLER AND CONNECT TONEAREST RECEIVER OUTSIDE OF COOLER.EXHAUST FAN. SWITCH FAN WITH RESTROOM LIGHTS, TYP.TELEPHONE BOARD: 4'X4'X3/4" PLYWOOD WITH (1) #6 CU.GROUND FOR FUTURE USE MOUNTED ABOVE 4'X4'X3/4"PLYWOOD WITH (1) #6 CU. GROUND PER TELE. CO.REQUIREMENTS.MOUNT RECEPTACLE ADJACENT TO ORABOVE TELEPHONE BOARD, DO NOT MOUNT BELOW.PROVIDE PAD-LOCKABLE BREAKER FOR MAINTENANCE PER N.E.C.422.31(B). COORDINATE EXACT LOCATION OF ELECTRICAL OUTLET WITHCONSTRUCTION MANAGER PRIOR TO ROUGH-IN.E.C. TO PROVIDE WIRING FOR COOLER AND/OR FREEZER DOORHEATERS AND DOOR FRAMES AND CONNECT TO MANUFACTURERSUPPLIED JUNCTION BOX(ES).22ISOLATED GROUND (IG) 20 AMP CIRCUIT FOR ATM, FLUSH MOUNTDUPLEX FACE PLATE WITH ORANGE RECEPTACLE.23GUTTER LOOPS - ROUTING OF ALL WIRING THROUGH GUTTER ANDBETWEEN PANELS AND OTHER WIRING DEVICES.24EXTERIOR SIGN J-BOX - OPTIONAL LOCATIONS OF EXTERIOR ATM SIGNIF SHOWN ON SIGNAGE PACKAGE.E.C. TO MAINTAIN 2" SPACING BETWEEN RECEPTACLES FOR STAND UPLOTTO MACHINE.2526RECEPTACLE FOR SPEAKER TO BE FLUSH MOUNTED DIRECTLY BEHINDSPEAKER. VERIFY EXACT HEIGHT AND LOCATION WITH ARCHITECTURALDRAWINGS. INSTALLER TO HIDE POWER CABLE BEHIND THE SPEAKERUSING CABLE TIES.WIREWAY TO COMPLY WITH WIREWAY SIZE, NUMBER OF CONTACTORS,AND REDUCTION FACTOR PER NEC 376.22 (A) & (B).2728CONTRACTOR TO INSTALL 12" X 12" WEATHER PROOF JUNCTION BOXFOR FUTURE SOLAR EQUIPMENT CONDUITS. SEE ROOF PLAN FORADDITIONAL REQUIREMENTS.E.C.TO INSTALL WEATHERPROOF J-BOX FOR RAYCHEM HEAT TRACEWHICH SUPPLIES FREEZE PROTECTION FOR FREEZER CONDENSATELINES. FURNISH HEAT TRACE AND PROVIDE GFI-EPD CIRCUIT BREAKERAND INSTALL PER MANUFACTURER'S REQUIREMENTS. REF.ELECTRICAL SPECIFICATIONS.Job#:
<br />Scale:
<br />Date:
<br />Drawn By:
<br />Checked By:
<br />Rev. #Date DescriptionSHEET:7-ELEVEN, INC.
<br />3200 HACKBERRY, IRVING, TEXAS 75063
<br />SE1237
<br />7-ELEVEN 1046249
<br />1110 MAIN ST
<br />MANTECA, CA 95336
<br />MS
<br />RES
<br />10/29/2020E1.0ELECTRICAL FLOOR PLAN
|