CLIENT:
<br /> HYDROSTATIC TEST LEAD CONNECTED TO GROUND ROD
<br /> TANK #2B\ RESERVOIR (NOT LUG OR WIRING)
<br /> / #4 STRANDED WIRE TO
<br /> O
<br /> 1/2"0 CADWELD GROUND 7 ,
<br /> HYDROSTATIC ROD CONNECTION — 10 OHMS MAX „ ,µ
<br /> l �
<br /> RESERVOIR 0 - #4 STRANDED WIRE TO 3 2 #4 STRANDED BARE 4ND
<br /> RA
<br /> D ED
<br /> 0 I 1/2"0 CADWELD GROUND BARE COPPER
<br /> ° I ROD CONNECTION GROUND TO
<br /> ° GROUND ROD TO OTHE
<br /> TURBINE SUMP FILL SUMP
<br /> �O(TYP.) [Fr a p
<br /> 6 (TYP.) tif 7
<br /> TO VENT STACK „
<br /> BOND GROUND WIRE TO 'T CADWELD #4
<br /> 3 FILL SUMP STRANDED BARE
<br /> ALL METALLIC RISERS
<br /> 1/2" 0 X 10' LONG 1 \ COPPER WIRE
<br /> \ AS REQUIRED (TYP.) COPPER CLAD STEELCONNECTION r �` 4"0 BRONZE PIPE
<br /> GROUND ROD DETAIL , + 6
<br /> GROUND ROD INSTALL OUTSIDE OF 1 3 SEE BONDING DETAIL GROUND ROD IN _ (TYP.) , CLAMPS (TYP.)
<br /> TANK EXCAVATION IN NATIVE SOIL / NATIVEARCO
<br /> 4
<br /> (TYP.) ( ,'
<br /> FILL SUMP
<br /> TERMINAL CONNECTION `' #4 STRANDED BARE 5
<br /> ° I ° 1. ,r `
<br /> i (D
<br /> ° > > COPPER GROUND TO
<br /> 0 0�
<br /> EQUIMMENT SCHEDULE ° 1 `� 3/4" 0 SOLID ROD
<br /> I I + + CADWELD L CONNECTION
<br /> NOTE: i ANCHORING PLATE i (TYP.) 0
<br /> TURBINE SUMP SEE TANK FUELING SITE PLAN 1 ® >,
<br /> ITEC FOR SPECIFIC TANK LAYOUT 3/4"0 x 12" LONG 8
<br /> DESCRIPTION , 4 DIA. BRONZE ,
<br /> NO. TANK 2A TAN 1 `�\ GROUND CLAMP 6 ', BRONZE ROD (TYP.)
<br /> 1/2" 0 X 10' LONG COPPERBONDED GROUND \ / \ / `� (NP`) ; � � E G� �
<br /> CD ROD: "ERICO" PART NO. 611,300 (UL LISTED)
<br /> OR EQUIVALENT RISER (TYP.}
<br /> 18215 72ND AVENUE SOUTH
<br /> O #4 AWG STRANDED BARE COPPER GROUND B B NOTE: KENT, WA 98032
<br /> 2 WIRE. PROVIDE TERMINAL CONNECTORS AT FOR PENETRATIONS OF THE SUMP WALLS, (425)251-6222
<br /> U—BOLT CONNECTIONSSOLID BRONZE STUD BOLTS ARE TO BE USED ®®® (425)251-8782 FAX
<br /> GROUND CLAMP-AT-FILL AND THE INTERIOR SUMP GROUND WIRES ARE
<br /> OCADWELD #4 WIRE CABLE TO GROUND ROD TO BE CONNECTED VIA TERMINAL CONNECTORS CML ENGINEERING, LAND PLANNING,
<br /> CONNECTION "ERICO" PART NO. GTT14A1 L, USE SUMP TO THE BOLTS. BOLTS TO BE SEALED BOTH SURVEYING, ENVIRONMENTAL SERVICES
<br /> NOTE:
<br /> WELD METAL #32 ,-'"`------------------------------------------ -------------------------------------------------------------_-,` INSIDE AND OUT WITH GLASS MATT & RESIN.
<br /> ALL EXTERIOR WIRE PENETRATIONS No. DATE REVISION DESCRIPTION '
<br /> CADWELD "T" CONNECTION FOR #4 BARE2 #4 STRANDED BARE ♦`
<br /> ARE REQUIRED TO BE CAD WELDED
<br /> COPPER GROUND �� TO ENSURE EFFECTIVE GROUNDING. 9
<br /> STRANDED WIRE CABLES. ERICO PART N0. 2 TO GROUND CLAMPS
<br /> `--� TAC1 L1 L USE #32 WELD METAL. ' A4 STRANDED �` z
<br /> BARE COPPER ON FILL RISERS
<br /> + #4 STRANDED BARE 2 GROUND
<br /> F 3/4" NPT ADJUSTABLE BRONZE GROUNDING COPPER GROUND TO OTHER TANKS „ + TYPICAL FILL SUMP 3
<br /> 5 3/4 GROUNDING 1
<br /> 5 PIPE CLAMP, LIND EQUIPMENT P/N JR-150-6 + TO GROUND ROD , 4
<br /> (905) 475-5086 ; CLAMP W/ TAP + EXTREME CAUTION MUST BE OBSERVED WHILE USING ANY NON—INTRINSICALLY SAFE
<br /> + SCREW (TYP.) ; DEVICE IN CLASSIFIED AREAS. SUMP MUST BE TESTED FOR VOLATILE VAPORS PRIOR s
<br /> TO USE. ELECTRICAL CONNECT MUST BE MADE WITH JUMPER WIRE SO FINAL o
<br /> O6 4" NPT ADJUSTABLE BRONZE PIPE CLAMP, 8 3/4"0 x 12" LONG i CONNECTION IS AWAY FROM CLASSIFIED AREAS.
<br /> LIND EQUIPMENT P/N JR-150-30 (905) , SOLID BRONZE ;
<br /> 475-5086 ; "T" CADWELD #4 4 ROD (TYP.) GENERAL SHEET NOTES
<br /> ' STRANDED BARE '
<br /> O POMECO/OPW 6110-12WT 12" H-20 RATED ; COPPER WIRE ° s {
<br /> ACCESS COVERJc
<br /> + CONNECTION , Q
<br /> ' (TYP.) + SCALE: NONE
<br /> 3/4"0 x 12" LONG SOLID BRONZE ROD ; NOTES: 11
<br /> TESTING: 9z
<br /> ALL STAGE I FILL AND VAPOR RISER ADAPTERS SHALL BE ELECTRICALLY GROUNDEDCAUTION: AVOID CONNECTING ANY ELECTRICAL TEST LEAD TO THE FILL OR VAPOR SEAL
<br /> O3/4" DOUBLE WALL ENTRY FITTING. j i TO PROMOTE THE RELAXATION OF STATIC CHARGE. RISER IN A MANNER THAT WOULD POTENTIALLY PRODUCE STATIC DISCHARGE OR Q�4 'ESSl
<br /> "BRAVO" MODEL NO. F-17 SS D + #4 STRANDED BARE COPPER 5 3/4" FRP BONDED ' THE BONDING AND GROUNDING FOR STATIC ELECTRICITY PROTECTION SHALL BE IN SPARKS OF ANY KIND. �® M°
<br /> \�
<br /> GROUND TO 3/4°' 0 SOLID ROD 9 DOUBLE ENTRY BOOT �� COMPLIANCE PER ALL APPLICABLE FEDERAL, STATE AND LOCAL CODES INCLUDING THE FILL AND VAPOR RISERS SHALL BE TESTED AFTER INSTALLATION AND
<br /> CADWELD "L" CONNECTION "BRAVO" MODEL N0. �% NEPA 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE, NFPA 77, RECOMMENDED PERIODICALLY TO VERIFY BONDING AND GROUNDING COMPETENCY.
<br /> (TYP.) EXTERNAL INTERNAL PRACTICE ON STATIC ELECTRICITY, NFPA 70, NATIONAL ELECTRIC CODE, AND THE
<br /> ( ) SUMP WALL SUMP WALL F-17—SS—D CALIFORNIA CODE OF REGULATIONS, SUBCHAPTER 15, PETROLEUM SAFETY THE MAXIMUM RESISTANCE FROM ANY FILL OR VAPOR ADAPTER TO THE BODY OF ^C 1
<br /> - ORDERS—REFINING, TRANSPORTATION AND HANDLING, ARTICLE 5, FIRE AND THE GROUND ROD SHALL NOT EXCEED 10 OHMS FOR A METALLIC RISER PIPE, SPILL dra
<br /> TYPICAL PENETRATION & CONNECTION DETAIL EXPLOSIONS. CONTAINMENT AND ADAPTER ASSEMBLIES.
<br /> Ao STATBC GROUNDIING PLAN VIEW & BONDIING DETAIILS (SEE INSTALLATION SEQUENCE NOTES BELOW) PER SECTION 6.4.1.3 OF NFPA 77, THE MEASURED TOTAL RESISTANCE IN THE THE RESISTANCE THROUGH ANY COMPOSITE OR NONMETALLIC STAGE I CONTAINMENT �,q, CIV 0-
<br /> SCALE: NONE GROUND PATH TO EARTH SHALL BE LESS THAN 1 MEGAOHM WHICH IS CONSIDERED FITTING SHALL BE MEASURED WITH A OHMMETER CAPABLE OF READING UP TO 10 ®F CA0�®
<br /> ADEQUATE FOR RELAXATION OF STATIC CHARGE. THE MAXIMUM ALLOWABLE GROUND MEGAOHMS. THE SUM COLLECTIVE RESISTANCE OF THESE SEMI—CONDUCTIVE
<br /> PATH TO EARTH RESISTANCE FOR STATIC ELECTRICITY GROUNDING APPLICATIONS ELEMENTS SHALL NOT EXCEED 100,000 OHMS. FOR THESE SYSTEMS, THE GROUND
<br /> SHALL NOT EXCEED 100,000 OHMS. RESISTANCE TESTER MUST BE CONNECTED TO THE GROUND CONDUCTOR CONNECTION
<br /> PER SECTION 6.4.1.3 OF NFPA 77, THE RESISTANCE IN METALLIC BONDING AND OR ON THE COMPOSITE CONTAINMENT SYSTEM OR RISER PIPE.
<br /> 7 12" H-20 RATED ACCESS COVER GROUNDING SYSTEMS SHALL BE LESS THAN 10 OHMS. RESISTANCE HIGHER THAN 10 FOR INSTALLATIONS WITHOUT AN EXPOSED GROUND ROD CONNECTION, TOTAL SYSTEM
<br /> --- OHMS INDICATES INADEQUATE CONNECTIONS. RESISTANCE SHALL BE MEASURED WITH A GROUND RESISTANCE TESTER BY A
<br /> A GROUNDING SYSTEM PER NEC CODE FOR CURRENT CARRYING CONDUCTORS SHALL QUALIFIED ELECTRICIAN FAMILIAR WITH GROUND TESTING. THE TWO POINT METHOD
<br /> �' `♦
<br /> CADWELD #4 WIRE CABLE TO GROUND ROD BE CONSIDERED MORE THAN ADEQUATE FOR A STATIC ELECTRICITY GROUNDING MAY BE USED WITH THE SITE ELECTRICAL GROUNDING AS THE SECOND TEST POINT.
<br /> 4" 3 OR GROUND ROD CLAMP SYSTEM. THE NEC MAXIMUM GROUND PATH RESISTANCE FOR CURRENT CARRYING
<br /> % MIN. `, PER THE NFPA 30, SECTION 5-6.3.4 ALL PARTS OF THE FILL PIPE ASSEMBLY, APPLICATIONS IS 25 OHMS. HOWEVER, GROUND ROD TO EARTH RESISTANCE UP TO
<br /> ` INCLUDING THE DROP TUBE, SHALL FORM A CONTINUOUS ELECTRICALLY CONDUCTIVE 100 OHMS SHALL BE ACCEPTABLE FOR STATIC ELECTRICITY PROTECTION OF THE FILL
<br /> � ; 1 1/2" � X 1 O' LONG COPPER
<br /> CLAD STEEL GROUND ROD IN 4" FILL AND PATH. AND VAPOR RISERS. DEVELOPMENT INFORMATION:+ ,
<br /> NATIVE SOIL STAGE I RETURN THE MINIMUM WIRE SIZE FOR BONDING AND GROUNDING SHALL BE COPPER AWG #4 ARCO NTI f
<br /> PIPES (TYP.) A 1/2" 0 BY 10 LONG COPPER CLAD STEEL GROUND ROD SHALL BE DRIVEN INTO
<br /> �� ,
<br /> NATIVE SOIL ONLY. PLACING THE GROUND ROD INTO TANK PIT PEA GRAVEL SHALL 3000 am/pm
<br /> \� �% \/ ' 2 #4. AWG STRANDED CONTAINMENT FILL SIDE NOT BE PERMITTED UNDER ANY CONDITIONS. THE CONTRACTOR IS RESPONSIBLE FOR NOTE: FUEL CANOPY
<br /> BARE COPPER NOT CLEARING ANY UNDERGROUND UTILITIES PRIOR TO INSTALLATION OF THE GROUND. ALL CAD WELDS W/ EXCEPTION OF FINAL CAD WELD @ GROUND ROD NOTED IN
<br /> GROUND WIRE BOX (TYP.) SUMP (TYP.) SCHEDULE BELOW MAY BE PREFABRICATED OUTSIDE THE TANK AREA AND BROUGHT (a MPS s
<br /> TANK TANK THE GROUND ROD TO GROUND WIRE CONNECTION SHALL BE ACCESSIBLE THROUGH A TO SITE.
<br /> 2
<br /> 4 H-20 RATED 12" DIAMETER MINIMUM ACCESS COVER TO ASSIST INSPECTION,
<br /> GROUND ROD DETAIL (n,P ) (TYP.) FINISHED MAINTENANCE AND TESTING. THE SCREW TYPE GROUND ROD CLAMP SHALL BE UL SITE ADDRESS:
<br /> SURFACE LISTED FOR DIRECT BURIAL.
<br /> ONE MAIN STRANDED #4 THHN CONDUCTOR SHALL BE RUN PAST EACH FILL SUMP.
<br /> °°°"° ONE STRANDED #4 THHN CONDUCTOR SHALL BE ROUTED TO EACH FILL SUMP. ®KZTtAY
<br /> X� INSTALLATION AT SUMP SHALL BE AS FOLLOWS AND MUST BE COMPLETED IN ORDER ESCALOA CA
<br /> \ \\ 5 6 \\/j�\� NOTED AS FOLLOWS:
<br /> 1/2" 0 X 10' LONG COPPER \ \ 8 (TYP.) \\\�\� FAMffY TBD
<br /> CLAD STEEL GROUND ROD IN 1 \� \�/��
<br /> //\ (TYP.) \\/\\� oEsic�vm BY: AwANCE zap:
<br /> NATIVE SOIL \\/\ \//�
<br /> AL
<br /> CHECKED 8Y: BP REP6fl:
<br /> OV
<br /> UBLE A
<br /> DRAWN BY: AWANCE PM:
<br /> COIL STATIC GROUND WIRE CABLE
<br /> WALL TANKS � � V-12°0: PROJECT No:
<br /> UP 3' & SECURE TO SIDE OF 2 12/14/2015 17223
<br /> GALVANIZED STEEL RISER PEAGRAVEL DRAWING TITLE:
<br /> BACKFILL
<br /> TANK FILL&VAPOR RISEN
<br /> \/\/� /\/\/\/� T�TI� ®EVIL
<br /> \ \i, „-- \\i/\\i/\\i/\\i/\\i/\\i/\\i" (CALIFORNIA ONLY)
<br /> , X �
<br /> EARTH �\�\��\��\��\�\��\��\
<br /> (GROUND ROD INSTALLED IN SOIL NOT PEAGRAVEL BACKFILL) SHEET NO:
<br /> NOTE:
<br /> ELECTRICAL CONDUIT, FUELING SYSTEM HARDWARE OR THE STATION ELECTRICAL
<br /> GROUNDING SYSTEM SHALL NOT BE USED FOR GROUNDING OR BONDING FILL AND GmOim7m2
<br /> Be STATIC GROUNDING SECTION & BONDIING DETAILS VAPOR RISERS.
<br /> SCALE: NONE
<br />
|