Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMPtUDC TEST (continued) <br /> Test Method Developed by ❑ Manufacturer 123 Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used , Incon Tester <br /> Sump/UDC ID UDC 112 UDC 914 UDC 616 UDC 718 <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 12° 12" 12" E 12" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 4" 4" 4" 4" <br /> (inches) <br /> Test Start Time ! 12:48 pm 12:48 pm 12:49 pm 12:49 pm <br /> Initial Reading 1 .9887 1 .0978 1 .6566 1 .8961 <br /> Test End Time 12:68 pm 12:68 pm 12:68 pm 12:58 pm <br /> Final Reading W 1 .9884 1 .0989 1 .6666 1 .8960 <br /> Change in Reading 0.0003 0.0005 0.0003 0.0001 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results El Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of i <br /> Highest Pipe Penetration ` <br /> (inches) I <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fall Criteria � <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additionai copies of this page may be attached. <br /> All tests marked "Failm and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />