Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMPIUDC TEST <br /> Test Method Developed by ❑ Manufacturer 0 Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 121 Hydrostatic <br /> Test Equipment Used : Incon Tester .. <br /> Sump/UDC ID 87 STP 91 STP Diesel STP <br /> Sump Manufacturer Fiberglass Fiberglass Fiberglass <br /> Sump Depth (inches) 64" 64" 6451 <br /> a <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 24° 2411 2211 ? <br /> (inches) <br /> Test Start Time 10 :44 am 10: 25 am 10 :25 am <br /> Initial Reading 4.9772 5.1354 5.x235 <br /> Test End Time� � <br /> 10 :69 am 10 :40 am 10 :40 am <br /> Final Reading 4.9778 5.1351 5x235 <br /> Change in Readingk 0.0005 0.0003 <br /> 0.0000 <br /> Pass/Fail Criteria 0.002 0.002 0.002 <br /> Tightness Test Results ID Pass ❑ Fail O Pass ❑ Fail � l Pass ❑ Fail ❑ Pass ❑ Fail <br /> SumpIUDC ID 87 FILL 91 FILL Diesel FILL <br /> Sump Manufacturer Fiberglass Fiberglass Fiberglass <br /> Sump Depth (inches) 6411 5410 4TQ6411Sump Bottom to Top of <br /> Highest Pipe Penetration NIA NIA NIA <br /> (inches) <br /> Test Start Time x:68 am 8 ,56 am 8 :68 am <br /> Initial Reading 3.8239 5.8817 3.2207 <br /> Test End Time 9: 11 am 9 : 11 am 9 : 11 am <br /> Final Reading 3.8227 5.8813 3.2201 <br /> Change in Reading 0.0012 0.0004 0.0006 <br /> Pass/Fail Criteria 0.002 0.002 0.002 <br /> Tightness Test Results ❑ Pass ❑ Fall O Pass ❑ Fail ; _I] Pass ❑ Fail ❑ Pass F . <br /> g , ail <br /> G <br /> Additional copies of this page may be attached <br /> All tests marked lair and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section , <br /> Page 3 of 5 <br />