Laserfiche WebLink
VALVE OPERATION <br />The Franklin Fueling Systems (FFS) Defender Series® Overfill Prevention Valve (OPV) is designed <br />with a primary shutoff that activates between 85 and 92% of tank volume, depending on the <br />tank diameter. When the primary shut-off is actuated, the flow through the OPV is limited to less <br />than 8 GPM (30 LPM). A secondary, positive shutoff happens at 95% tank volume if you continue <br />filling. After primary shutoff, you can still drain the delivery hose, but you must be extremely <br />careful and follow these steps: <br />1. Close the truck bottom loading valve. <br />2. Wait 5 minutes. <br />3. Partially open the coupler between the delivery hose and the bottom loading valve and <br />allow the hose to drain. <br />NOTE: Shutoff points are affected by the specific gravity of the stored liquids. These instructions <br />are based on the average performance of all products. The OPV was designed to be only an <br />emergency overfill prevention device. <br />NOTE: Determine if the underground storage tank has a ball float vent valve. If it does, make sure <br />the nipple portion does not extend more than 3" (76.2 mm) into the tank. <br />TANK SIZE AND INSTALLATION OF OVERFILL PREVENTION DEVICES <br />In a two-stage, mechanical Overfill Prevention Valve (OPV), primary closure of the device <br />significantly restricts the flow of fuel into the tank. After primary shut-off occurs, the delivery <br />hose can be drained slowly 3-5 GPM (11-18 LPM) until secondary or "positive" shut-off occurs. <br />Under current EPA regulations and industry standards, secondary shut-off is typically set at 95% <br />of tank volume; however, other local regulations may prescribe other values. <br />Mechanical OPVs use a float(s) to trigger shut-off, or closure, of the device and restrict flow to <br />the storage tank. The shut-off level of the secondary ("positive") closure can be set based on <br />the height of installation in the tank. The height of this installation typically is correlated with a <br />volume percentage such as 95%. The level of the primary shut-off point will fluctuate to some <br />degree based variables such as the: <br />• Size and shape of the tank. (See the images below.) <br />• Specific gravity of the stored liquid: <br />The offset picture is based on a specific gravity of 0.75 for gasoline and 0.85 for diesel. A <br />lower specific gravity will need more fluid to create equivalent buoyancy, which equates to a <br />higher shutoff level (and vice -versa). <br />• Flow rate during delivery. <br />The offset is based off data from our production flow test apparatus, which runs at 370 <br />gpm. A lower flowrate causes less buoyancy force needed to activate the primary, which <br />equates to a lower shutoff level. <br />The most influential of these variables is the size and shape of the tank volume, as illustrated <br />below. Always use a calibrated tank chart in combination with the manufacturer's instructions for <br />best results. <br />