Laserfiche WebLink
rPEIlRP1200-12 <br />pipe, it is not considered to be liquid -tight. This <br />visually indicates a test failure. <br />6.3.5 Test Procedure. <br />1. Slowly apply a vacuum of 30 inches water <br />column to the spill bucket and close the valve. <br />If a 30 -inch water column vacuum cannot be <br />attained, the spill bucket fails the test. See <br />Appendix B for pressure and vacuum conver- <br />sions. <br />2. Start the time -measurement device and record <br />the initial vacuum level shown on the gauge. <br />3. After 1 minute, record the ending vacuum level. <br />Upon completion of the test, release the vacuum, <br />remove the test apparatus and the Basketing mate- <br />rial from the spill bucket and replace the original <br />cover. <br />FIGURE 6-3. The vacuum test method can detect a spill <br />bucket leak by measuring the change in vacuum level <br />during the test. <br />6.3.6 Pass/Fall Criteria. If the ending vacuum <br />level is 26 inches water column or greater, the spill <br />bucket passes the test. <br />If the ending vacuum level is less than 26 inches <br />water column, the spill bucket fails the test. <br />and secondary containment. The vacuum level is <br />monitored for a 1 -minute period. <br />6.4.3 Test Equipment. Test equipment shall <br />include: <br />vacuum test apparatus (The test apparatus may <br />be available from the spill -bucket manufacturer. <br />It includes an air pressure regulator, a vacuum <br />source, a vacuum gauge with a minimum 0.30 <br />inch water column range, a test fitting and a <br />control valve. The control valve is used to adjust <br />the vacuum level.); <br />• stopwatch or other time -measurement device <br />capable of measuring a 1 -second increment. <br />WARNING. Use only an air -operated vacu- <br />um source or a vacuum pump powered by <br />an explosion -proof motor. Vacuum pumps <br />with electric motors that are not explo- <br />sion -proof may ignite flammable vapors. <br />If a portable air compressor is used, it <br />should be located at least 20 feet away <br />from the venturl-eductor or outside any <br />Class I, Division 1 area. <br />6.4 Double -Walled Spill Bucket Integrity Testing -- FIGURE 6-4. Check lines and connections to ensure <br />Vacuum Test Method. that they are leak -tight before starting the test. <br />6.4.1 Purpose. This method is used to test the <br />integrity of the primary and secondary containment <br />of the double -walled spill bucket. <br />6.4.2 Description of Test. A partial vacuum is <br />applied to the interstitial space between the primary <br />0 peLorg <br />6.4.4 Preparation. <br />1. Remove and properly dispose of any liquid and <br />debris (leaves, sediment and trash) in the spill <br />bucket. <br />