Recommended Practices for the Testing and Verification of Spill, Overfill, Leak Detection and Secondary Containment Equipment at UST Facilities <br /> 2 . Clean the spill bucket and examine it for dam- 6 . 5.1 General . Containment sumps are liquid- <br /> age. Make sure that it is free of cracks, loose tight structures designed to temporarily contain <br /> parts or separation of the bucket from the fill leaks or spills . In addition, containment sumps <br /> pipe. If the spill bucket is damaged notify the often serve as the leak detection monitoring loca- <br /> owner/operator. tion foil double-walled piping systems. Leakage <br /> 3 . Attach the test apparatus to the test porta from the primary containment typically flows by <br /> gravity inside the secondary containment to the <br /> 4 . Connect the line from the vacuum source to the sump, where it can be easily observed or detected <br /> lest apparatus. by a sensor. <br /> 5. If the spill bucket is found to have cracks , loose This section describes a hydrostatic test method. <br /> parts or separation of the bucket from the fill There are vacuum test methods available for con- <br /> pipe, it is not considered to be liquid- tight. This tainment sumps. Consult the manufacturer before <br /> visually indicates a test failure. performing a vacuum test. <br /> 6. 4. 5 Test Procedure. <br /> NOTE : Follow the manufacturer ' s instructions <br /> 1 . Slowly apply a vacuum of 15 inches water when testing the interstitial spaces of double,, <br /> column to the spill-bucket interstitial space and walled containment sumps , <br /> close the control valve. If a 15 -inch water col- <br /> umn vacuum cannot be attained, the spill bucket 6. 5. 2 Purpose : This section describes the prep,, <br /> falls the test . See Appendix B for pressure and aration and procedures to test the integrity of con- <br /> vacuum conversions , tainment sumps to ensure that they do not leak. <br /> 2. Start the time-measurement device and record 6. 5.3 Description of Test . The containment <br /> the initial vacuum level shown on the gauge. sump is filled to the proper level with water. The <br /> 3 . After 1 minute, record the ending vacuum level . water level is measured at the beginning and end of <br /> the test. <br /> Upon completion of the test, release the vacuum, <br /> remove the test apparatus and restore the spill 6 . 5.4 Test Equipment. Test equipment shall <br /> bucket to its normal operating condition . include : <br /> 6. 4 .6 Pass/Fall Criteria . If the ending vacuum water; <br /> level is 12 inches water column or greater, the spill measuring stick that is accurate to within 1/ 16 <br /> bucket passes the test. (0 .063) inch and of sufficient length ; <br /> If the ending vacuum level is less than 12 inches stopwatch or other time-measurement device <br /> water column, the spill bucket fails the test@ capable of measuring a 1 -second increment. <br /> 6 . 5 Containment Sump Integrity Testing. 6 . 5. 5 Preparation . <br /> 1. Care should be taken when conducting the test <br /> CAUTION : Gaining access to the contain- in the rain or during freezing weather condi - <br /> ment sump requires removing the lid , lions , <br /> cover or dispenser panel that is in place to <br /> protect the equipment in the sump . These 2 • Remove and properly dispose of any liquid and <br /> components can be heavy. They may debris (leaves , sediment and trash ) in the con- <br /> require special handling and more than lainmenl sump , <br /> one person to remove them . Use caution 3 . Inspect the containment sump for damage. <br /> when moving and replacing them when Examine all penetration fittings , conduits , junc- <br /> testing Is complete . During the test, put tion boxes, caps and risers (if present) , and side- <br /> the covers and panels in a safe location wall seams for defects , damage or impropez•ly <br /> where they are secure and isolated from installed components . If there are loose com- <br /> vehicle and customer traffic . ponents (e.g. , loose penetration fitting clamps <br /> or missing interstitial space caps) , correct these <br /> items before performing the integrity test. If <br /> pei .org <br />