Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by El Manufacturer ❑1= Industry Standard 0 Professional Engineer <br /> Test Type 0 Pressure 0 Vacuum E Hydrostatic <br /> Test Equipment Used: OMNTEC <br /> Sump/UDC ID 87 STP Diesel Disp STP Diesel Loader STP UDC 1-2 <br /> Sump Manufacturer Xerxes Xerxes Xerxes Xerxes <br /> Sump Depth (inches) 60 60 60 18 <br /> Sump Bottom to Top of 14 14 14 8 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 12:00 12:00 12:00 13:05 <br /> Initial Reading 9.047 9.433 11.867 8.103 <br /> Test End Time 12:15 12:15 12:15 13:20 <br /> Final Reading 9.047 9.433 11.867 8.103 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria 0.0020 0.0020 0.0020 0.0020 <br /> Tightness Test Results E Pass rl Fail El Pass ® Fail F1 Pass ® Fail 0 Pass © Fail <br /> Sump/UDC ID UDC 3-4 <br /> Sump Manufacturer Xerxes <br /> Sump Depth (inches) 18 <br /> Sump Bottom to Top of 8 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 13:05 <br /> Initial Reading 8.504 <br /> Test End Time 13:20 <br /> Final Reading 8.504 <br /> Change in Reading 0 <br /> Pass/Fail Criteria 0.0020 <br /> Tightness Test Results 0 Pass 97 Fail 0 Pass El Fail © Pass g7 Fail r Pass Ll Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />