Laserfiche WebLink
STEP 25: INSTALL WARNING PLATE <br /> Bend the three warning plate ears down then slide the <br /> tie wrap Diner the warm ng qWe ears and position waro- <br /> ing plate against Wiser pipe approatirrwtely 1"below the <br /> adaptor, Tighten the tia wrap securely. The vah►e is <br /> rlow fully installed and in operating positron_ <br /> 46 <br /> NOM the warning p4Re inGhtdes bnp w at ware- <br /> ing%opensting puamews,acid Jistkg Infomnation OrW <br /> and must be instaM�d. mar <br /> yI <br /> o0o <br /> Manufacturer:"OP4Ar` <br /> Model:'71 SO-0` <br /> (4'represents sEae) <br /> Manufacture Date: <br /> 4AFG MMYY' <br /> MJV1—Nbnth YY-Year <br /> I �~4 <br /> Flom 26-Product fdend&atlon <br /> STEP 26:VALVE REMOVAL <br /> The vaiw can be removed for tank leak testing.Inspm- <br /> tion,etc,by removing the Rotatable Product Adaptor, <br /> the 4"nipple,and the lack Screw Kit. ReinstaJ l per the <br /> above Instructions. <br /> For t*Mble models only: It is not necessary to re- <br /> move the valve to check poppet movement f function. <br /> ge <br /> See Pa17 for full testing details. <br /> STEP 27: ELECTRONIC LIQUID LEVEL MONITORING <br /> If an electronic level mon!tor is 1nmalied,it must be caH- <br /> brated to match the top of the 71 SO valve body,which <br /> must correlate with 95%of the antral tank capacity, <br /> 16 <br />