SAN J 0 A Q I I I Irl Environmental Health Department <br /> CCUNr <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> WEST VALLEY AUTO SERVICE LLC 2615 W GRANT LINE RD,TRACY March 28, 2023 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 307 HSC 25290.1(c3), 25290.2(c3) Failure to keep water out of the secondary containment system (post-Jul 2003). <br /> OBSERVATION:Water was found in the following locations: <br /> -Vent sump <br /> -91-grade fill sump <br /> -Diesel submersible turbine pump(STP)sump <br /> -UDC 3/4 <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any water intrusion into the <br /> system by precipitation, infiltration, or surface runoff. <br /> CORRECTIVE ACTION: The service technician removed approximately 1/2 a gallon of liquid from the vent sump, <br /> 91-grade fill sump, diesel STP sump, and UDC 3/4 and returned the sensor to its proper location. Immediately <br /> contact a properly licensed,trained, and certified contractor to address the water intrusion into the vent sump, 91 fill <br /> sump, diesel STP sump and UDC 3/4 under permit and inspection of the EHD. <br /> This is a repeat violation, Class Il. <br /> 317 CCR 2636(f)(2) Failure of the line leak detector to detect a 3.0 gph leak at 10 psi and restrict or shut off flow. <br /> OBSERVATION: The Diesel line leak detector failed to detect a leak when tested at UDC 7/8. <br /> REGULATION GUIDANCE:All line leak detectors shall be capable of detecting a 3-gallon per hour leak at 10 psi. <br /> CORRECTIVE ACTION: Immediately have a properly licensed,trained, and certified contractor repair or replace the <br /> failed leak detector and obtain a permit within one business day from the EHD, if needed. If the failed leak detector <br /> can't be replaced immediately,there is a possibility that the Diesel UST system may be red tagged to prevent fuel <br /> inputs. <br /> This is a repeat violation, Class Il. <br /> Overall Inspection Comments: <br /> An inspection checklist was provided to the facility operator on the day of inspection. A complete report was <br /> finished on 3/28/2023 and replaces the initial checklist. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, within 30 days of receiving the complete inspection report. <br /> NOTE: This facility currently uses an audible/visual overfill prevention method. <br /> FA0014623 PR0521537 SCO01 03/28/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 5 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />