Laserfiche WebLink
Underground Storage Tank <br />Secondary Containment Testing Report Form <br />8. SUMP/UDC TEST <br />Test Method Developed by El Manufacturer ® Industry Standard in Professional Engineer <br />Test Type ® Pressure ® Vacuum ® Hydrostatic <br />Test Equipment Used: Caldwell Sump Level Change Indicator <br />Sump/UDC ID <br />882-TFUD01 Sump <br />Sump Manufacturer <br />Western FG <br />Sump Depth (inches) <br />36.00" <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />17.75" <br />Test Start Time <br />9:07a <br />Initial Reading <br />19.75" <br />Test End Time <br />9:57a <br />Final Reading <br />19.74" <br />Change in Reading <br />-0.01" <br />Pass/Fail Criteria <br />< 0.1 Ogph <br />Tightness Test Results <br />® Pass rl Fail <br />rl Pass rl Fail <br />® Pass ® Fail <br />® Pass ® Fail <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />Test Start Time <br />Initial Reading <br />Test End Time <br />Final Reading <br />Change in Reading <br />Pass/Fail Criteria <br />Tightness Test Results ® Pass ® Fail ® Pass ® Fail ® Pass ® Fail rl Pass r Fail <br />Additional copies of this page may be attached. <br />All tests marked "Fail' and any repairs made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 3 of 5 <br />