Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for SINCLAIR NORTH MAIN as of July 13, 2023. <br /> Open violations from May 08, 2023 inspection <br /> Violation#307-Failure to keep water out of the secondary containment system (post-Jul 2003). <br /> OBSERVATION:Water was found in the 87 and 91 fill sumps, 87, 91, diesel spill containers, 87 and diesel STP <br /> sumps. <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any water intrusion into the <br /> system by precipitation, infiltration, or surface runoff. <br /> CORRECTIVE ACTION:The service technician removed 17 gallons of liquid from the 87 and 91 fill sumps, 87, 91, <br /> diesel spill containers, 87 and diesel STP sumps and returned the sensor to its proper location. Immediately contact <br /> a properly licensed,trained, and certified contractor to address the water intrusion into the 87 and 91 fill sumps, 87, <br /> 91, diesel spill containers, 87 and diesel STP sumps under permit and inspection of the EHD. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Page 5 of 5 <br />