Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by ® Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: F.F.S. Incon TS-STS Sump Tester w/ + or—0.002" graduations <br /> Sump/UDC ID UDC 7 UDC 10 UDC 8-9 <br /> Sump Manufacturer Bravo Bravo Bravo <br /> Sump Depth (inches) <br /> 12" 12" 12" <br /> Sump Bottom to Top of Piping come in Piping come in Piping come in <br /> Highest Pipe Penetration from bottom of from bottom of from bottom of <br /> inches UDC UDC UDC <br /> Test Start Time 9:40am 9:40am <br /> Initial Reading 3.5519" 3.0705" <br /> Test End Time 9:55am 9:55am <br /> Final Reading 3.5521 3.0705" <br /> Change in Reading +0.0002" 0.00" Visual Fail <br /> Pass/Fail Criteria + or— 0.002" + or— 0.002" + or— 0.002" + or— 0.002" <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ® Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria + or— 0.002" + or— 0.002" + or— 0.002" + or— 0.002" <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />