Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for Sunwest Chevron as of January 09, 2024. <br /> Open violations from October 17, 2023 inspection <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Violation#307-Failure to keep water out of the secondary containment system(post-Jul 2003). <br /> OBSERVATION:Water was found in the diesel and 87 STP sumps. <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any water intrusion into the <br /> system by precipitation, infiltration, or surface runoff. <br /> CORRECTIVE ACTION: Immediately remove this liquid, make a hazardous waste determination per Title 22 <br /> hazardous waste regulations, and manage accordingly. Immediately contact a properly licensed, trained, and <br /> certified contractor to address the water intrusion into the STP sumps under permit and inspection of the EHD, if <br /> needed. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Page 6 of 6 <br />