The following is an itemized list of CP22 - UST FULL violations that have not been <br /> addressed forAHMEDS SONS INC as of August 26, 2024. <br /> Open violations since July 03, 2024 inspection <br /> Violation#9-2030002-Leak detection equipment tested by qualified service technician every 12 months <br /> (TCR 9d). <br /> OBSERVATION: The annual monitoring system certification and leak detector testing were last performed on <br /> 4/11/2023 and were due by May 2024. Testing has not been completed for the 87, 91, and Diesel annular sensors and <br /> is 3 months past due. <br /> REGULATION GUIDANCE: These tests are required once every 12 months. <br /> CORRECTIVE ACTION: Immediately schedule these tests and provide 48 hours notification to the EHD. Please be <br /> aware that all EHD staff time associated with a follow up inspection will be billed at our current hourly rate�($156). <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> ! <br /> Violation#11 -2030048-Sec containment testing conducted per requirements&records kept for 36 mths <br /> (TCR 9d). <br /> OBSERVATION: Secondary containment testing was last performed on 5/11/2021 and was due by May 2024. Testing <br /> has not been completed and is over 1 month past due. <br /> REGULATION GUIDANCE: Secondary containment testing is required to be performed once every 36 months. <br /> CORRECTIVE ACTION: Immediately schedule this test and provide 48 hours notification to the EHD. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included r—_ _ r <br /> Describe actions taken or will be taken to correct violation: '�1 <br /> Page 1 of 2 <br />