Laserfiche WebLink
SAN ,,] DAQ U I <br /> N Environmental Health Department <br /> C C u T IV AMENDED <br /> 3/19/2024 <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> SGS Stockton-Carpenter Road 4863 CARPENTER RD, Stockton March 14, 2024 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 619 CFR 112.7(e), 112.8(c)(6) Failure to keep written records of procedures, inspections, and tests for at least three <br /> years. <br /> OBSERVATION: The facility failed to keep written procedures and records of inspections and tests. Facility failed to <br /> follow inspection procedures for the oil storage containers following section 4.6 of the SPCC plan. <br /> 1. Facility did not have monthly inspection records for the four Crop Oil poly tanks for the last three years. <br /> 2. Facility did not have annual inspection records for the last two years for the four Crop Oil poly tanks. <br /> 3. Facility did not have any inspection records for Rinse Water Totes for the last three years. <br /> 4. Facility did not have the annual inspection records for the gasoline tank for 2022. <br /> REGULATION GUIDANCE: 112.7(e), Conduct inspections and tests required by this part in accordance with <br /> written procedures that you or the certifying engineer develop for the facility.You must keep these written <br /> procedures and a record of the inspections and tests, signed by the appropriate supervisor or inspector,with the <br /> SPCC Plan for a period of three years. Records of inspections and tests kept under usual and customary business <br /> practices will suffice for purposes of this paragraph. <br /> 112.8(c)(6)Test or inspect each aboveground container for integrity on a regular schedule and whenever you make <br /> material repairs.You must determine, in accordance with industry standards,the appropriate qualifications for <br /> personnel performing tests and inspections,the frequency and type of testing and inspections,which take into <br /> account container size, configuration, and design (such as containers that are: shop-built,field-erected, <br /> skid-mounted, elevated, equipped with a liner, double-walled, or partially buried). Examples of these integrity tests <br /> include, but are not limited to: visual inspection, hydrostatic testing, radiographic testing, ultrasonic testing, acoustic <br /> emissions testing, or other systems of non-destructive testing.You must keep comparison records, and you must <br /> also inspect the container's supports and foundations. In addition, you must frequently inspect the outside of the <br /> container for signs of deterioration, discharges, or accumulation of oil inside diked areas. Records of inspections <br /> and tests kept under usual and customary business practices satisfy the recordkeeping requirements of this <br /> paragraph. <br /> CORRECTIVE ACTION: Inspections and tests must be conducted in accordance with the written procedures <br /> developed in the Spill Prevention, Control, and Countermeasure(SPCC) Plan. Records of these inspections and <br /> tests must be signed by the appropriate supervisor or inspector and kept on-site with the SPCC Plan for three <br /> years. Immediately locate a copy of all inspection and testing records for the last three years, maintain them <br /> on-site, and submit copies to the EHD. <br /> This is a Class II violation. <br /> FA0005712 PR0538368 SCO01 03/14/2024 <br /> EHD 28-01 Rev.12/06/2021 Page 10 of 15 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />