Laserfiche WebLink
4 <br />For your convenience, I added boxes around the tank sizes and weights on the buoyancy calculations and <br />tank cut sheets. <br /> On the application for UST Tank Installation Permit, page 3 of 8, needs the “Hazardous waste Certificate” <br />and “Workers Comp #”. See snippet. <br />o <br />The project does not include hazardous waste removal. The workers comp # has been added to the UST <br />Tank Installation Permit. I have also attached the workers compensation document. <br /> Page 7 of 8 of the application, Section G, you have listed the 71SO-410C-EVR but on the FM-1 page there <br />are two Overfill Prevention. Please clarify which overfill prevention you will be using. <br />o <br />On sheet FM-1, he 4”x13’ drop tube has been eliminated and the 4”x19’ drop tube w/overfill prevention <br />valve part number has been updated to 71SO-41C. <br />On 7 of 8 of the application, Section G, the part number has been updated to 71SO-410C to match FM-1. <br /> Page 8 of 8, Section I, alarm panel needs clarification. The FM-2 page list a different model number. <br />On FM-2, part number 200 has been updated to 860091-302. Page 8 of 8 Section I alarm panel model number <br />has been updated to 860091-302 to match FM-2. <br /> FT-1, section B, needs clarification for the drop tube. Per Xerxes cut sheet, “Service Fitting on Flat #25 is <br />for vent only.” <br />On FT-1, section B, the drop tube has been switched with the vapor/vent connection. The “Service Fitting on Flat <br />#25” is now a vent connection per the Xerxes cut sheet. <br />On FT-5, section A & B, has been updated to be a regular only fill sump. <br />Sheet FT-5.1 has been added for the new Premium Fill sump section A & B. <br /> FT-2, section A & B needs clarification for the drop tube/fill risers. Per Xerxes cut sheet, the placement of <br />the drop tubes should not be place in those locations.