Laserfiche WebLink
PO BOX 1928 <br />BENICIA, CA 94510 <br />TEL 707 346 5058 <br />FAX 707 922 2284 GEORGE REED INC. STI SP001 EXTERNAL INSPECTION <br />ESCALON, CA <br /> www.powerseicom 7,000 GALLONS OIL TANK <br /> <br />STI-SP001 External George Reed Inc. Escalon, CA Tank 7,000 Gal October 2024 Project #24-378 Rev0 <br />© 2024 PEI Inc. Page 14 of 43 Date Printed: 11/7/24 7:42 AM <br /> <br />4. Drawings <br /> 18-IN MANWAY CL: 3224-IN MANWAY COVER26-IN X 50-IN WASHOUT31-IN X 55-IN WASHOUT COVER1-IN THREADED COUPLING CL: 302-IN WELDED NOZZLE CL: 303-IN INLET NOZZLE CL: 29.5 RPD:6-IN X 6.5-IN1-IN THREADED COUPLING CL: 6.51.5-IN WELDED NOZZLE CL: 6.51-IN THREADED COUPLING CL: 6.51.5-IN WELDED NOZZLE CL: 6.53-IN THREADED COUPLING CL: 126-IN WELDED LOWER NOZZLE CL: 122.5-IN THREADED COUPLING CL: 29.756-IN WELDED HIGHER NOZZLE CL: 29.75PIPINGSUPPORT CONDUITPRODUCT RESIDUE SPLATTERED ON COVER <br />WORN/CRACKING GASKET <br />MINOR COATING FAILURE ON NECK <br />LIGHT RUSTING ON COVER <br />LIGHT RUSTING ON SOME HARDWARE <br />D-RING AND PIVOT MOUNT <br />NOT COATED /LIGHT RUSTING <br />WORN/CRACKING GASKET <br />PRODUCT RESIDUE SPLATTERED <br />ON COVER AND NECK <br />MINOR COATING FAILURE AND LIGHT RUSTING <br />ON COVER AND VERY MINIMAL ON NECK <br />BOTH ENDS ARE VISIBLE AND <br />NOT CONNECTED TO ANYTHING <br />MINO <br />R <br />C <br />OATIN <br />G FAILU <br />RE A <br />N <br />D LI <br />G <br />HT <br />R <br />USTIN <br />G <br />ON TA <br />NK SHELLCABLE LEVER SYSTEM