Laserfiche WebLink
PO BOX 1928 <br />BENICIA, CA 94510 <br />TEL 707 346 5058 <br />FAX 707 922 2284 711 MATERIALS INC. STI SP001 EXTERNAL INSPECTION <br />WATERFORD, CA <br /> www.powerseicom 12,000 GALLONS DIESEL TANK <br /> <br />STI-SP001 External George Reed Inc. Escalon, CA Tank 7,000 Gal October 2024 Project #24-378 <br />Rev0 <br />© 2024 PEI Inc. <br />Page 15 of 43 Date Printed: 11/7/24 7:42 AM <br /> <br />5. Venting Analysis <br /> <br /> <br />ft <br />ft <br />ft <br />gal <br />sq. ft <br />in <br />mmHg <br />in <br />in *Pipe sizes apply only to open vent ≤ 12-in long <br />in <br />in <br />SCFH <br />0 gpm 0 gpm <br />0 7 <br />38 °1 <br />0 SCFH Air 0 SCFH Air <br />122 SCFH Air 1,481 SCFH Air <br />122 SCFH Air 1,481 SCFH Air <br />Normal Vent: <br />Open Vent <br />1 Pressure Capacity Vacuum Capacity <br />4 in 16,500 SCFH 16,500 SCFH <br />0 in 0 SCFH 0 SCFH <br />0 in 0 SCFH 0 SCFH <br />0 in 0 SCFH 0 SCFH <br />0 in 0 SCFH 0 SCFH <br />16,500 SCFH 16,500 SCFH <br />Emergency Vent: <br />1 Pressure Capacity Vacuum Capacity <br />0 in 0 SCFH 0 SCFH <br />0 in 0 SCFH 0 SCFH <br />0 in 0 SCFH 0 SCFH <br />0 SCFH 0 SCFH <br />16,500 SCFH 16,500 SCFH <br />Shop Fabricated AST <br />Thermal In Breathing, Vit <br />Venting Recommendations based on Wetted Area as per NFPA 30 & UL 142 <br />9.86 <br />15.3 <br />NA <br />3500 <br />NA <br />343,052 <br />Venting area >= 90% In/Out, Existing venting area is Ok as per NFPA 30 21.4.3.3. <br />Normal vent shall be sized using either API 2000/another approved standard or shall be at least as <br />large as the largest inlet/outlet nozzle, but no less than 1.25-in diameter. <br />Normal Venting Capacity Check (API 2000) : <br />Normal Venting Capacity <br />Emergency Venting Capacity <br />Number of Emergency Vents <br />Size of Emergency MW w/ Long Bolt <br />NA <br />Class 3B <br />Lube Oil <br />474 <br />4 <br />Normal In Breathing (Vacuum) <br />Product Flow Rate Out, Vpf <br />C Factor for VP, T, and Latitude <br />Insulation Factor, Ri <br />Total Normal In Breathing Required <br />In Breathing due to Discharge, Vip <br />Tank SS-1 is equippped with 1 normal vent (4-in) and 1 emergency vent ( ). The size of the largest nozzle is 4-in. <br />The tank requires 122 SCFH of out-breathing and 1,481 SCFH of in-breathing at normal condition. The required emergency venting capacity is 343,052 SCFH. <br />Venting area >= 90% In/Out, Existing venting area is Ok as per NFPA 30. As per API 2000 calculation, the existing Normal Venting capacity is sufficient. <br />The existing total venting on the tank is 16,500 SCFH. Emergency venting capacity is insufficient. <br />Venting system recommendation for this tank is 4-in normal vent, 8-in emergency vent. <br />Venting capacity for pressure is sufficient. Venting capacity for vacuum is sufficient. <br />Min. Nominal Pipe Size, Normal Vent: <br />Min. Nominal Pipe Size, Normal Vent, for tank with manhole <br />as emergency vent: <br />Min. Nominal Pipe Size, Emergency Vent : <br />Emergency Vent Size, without Screen: <br />Emergency Vent Size, with Screen: <br />4-in or larger, unless API 2000 or <br />pumping rate capacity is less than <br />capacity of piping <br />2 <br />8 <br />NA <br />Vent Type <br />Thermal Out Breathing, Vot <br />---- <br />Emergency Venting Capacity Check (UL 142 & NFPA 30): <br />*If Unknown, PVV capacity is based on Varec PVV at 0.85" wc. Open vent <br />capacity is based on S&J Free Vent at 0.85" wc. Verify with manufacturer <br />for specific vent capacity. <br />Emergency venting capacity is insufficient. <br />Total Normal Out Breathing Required <br />Normal Out Breathing (Pressure) <br />Product Flow Rate In, Vpf <br />Vent Options (API 2000): <br />4-in normal vent, 8-in emergency vent <br />4-in normal vent <br />Vent Options (UL 142 & NFPA 30): <br />Emergency Venting Capacity Required: <br />*VP is unknown or larger than Hexane <br />(130mmHg at 20C) <br />Conclusion: <br />VENTING CONFIGURATION <br />API 2000 Venting Calculation for Atmospheric and Low Pressure Tanks <br />Existing Venting Adequacy <br />Normal Venting Size Check (NFPA 30) : <br />Size of Emergency Vent 2 <br />Size of Emergency Vent 1 <br />Total Existing Normal Venting Capacity: <br />Total Venting Capacity on Tank (Normal + Emergency): <br />Total Existing Emergency Venting Capacity: <br />Number of Normal Vents <br />Size of Goose Neck Vent 1 (in) <br />Size of Vapor Recovery Unit (in) <br />Size of Vent 4 (in) <br />Size of Vent 3 (in) <br />VENTING SELECTION (SP001, NFPA30, UL142, API2000) <br />Size of Largest Product In/Out Nozzle : <br />Size of Vent 2 (in) <br />Tank Shape <br />Capacity <br />Wetted Area <br />Product <br />Product Class <br />Vapor Pressure at 20 °C, VP <br />Tank Type <br />Fill Height, H <br />Diameter or Width, D/W <br />Length, L <br />Vertical Cylindrical <br />Tank ID <br />Factor for Latitude, Y <br />Latitude <br />Out Breathing due to Filling, Vop <br />SS-1