SAW dOAQUIN Environmental Health Department <br /> CCDuNT Fc EyDED <br /> 6/20/2025 <br /> RI - - UL2C NLgg TnFpe: tion Seport <br /> Na:ilitAyamed Na:ilitAFssrePPd Dated <br /> FLYING J TRAVEL PLAZA#618' 1 1501 N JACK TONE RD, RIPON May 13 2025 <br /> 2 L c c F SY ON VAgFCAy 2 <br /> (RgF 22 T RgF22 7[or c-5F OS Uy oti:a to Rompll� <br /> -gem# SemarkP <br /> OBSERVATION:The Tank 2 diesel VMI line leak detector failed to detect a leak when tested. <br /> REGULATION GUIDANCE:All line leak detectors shall be capable of detecting a 3-gallon per hour leak at 10 psi. <br /> CORRECTIVE ACTION: The service technician adjusted the leak detector, retested it, and it passed. <br /> This was corrected on site. <br /> This is a repeat violation (Class 2) Violation. <br /> 59 CA Code of Regulations 2712(b)(1-2)2030001 -Records of release detection monitoring and maintenance properly <br /> maintained (TCR 9d). <br /> OBSERVATION: Maintenance and monitoring records for the last three years were not found on site. <br /> - 9/19/2024&3/11/2025 Overfill Prevention test result <br /> -4/12/2025 The sensor was replaced, like for like, using (PN: 734380-303)located at L 11 ANNULAR PREM. No MSC <br /> and work order. <br /> - 11/28/2023 Secondary Containment Test <br /> -Work orders for 8/30/2024, 10/8/2024 <br /> -4/18/2025 Sensor was replaced, like for like, using (PN: 330020-463)located at S2 T1 RV DIESEL FP19.20 Missing <br /> work order and MSC <br /> -4/18/2025 Sensor 794380-303 was replaced. Missing work order&MSC <br /> -4/24/2024 for a T1 TANK DIESEL PROBE OUT ALARM.The probe was replaced, like for like, using (PN: <br /> 846397-407) located at T1. Missing work order& MSC. <br /> REGULATION GUIDANCE: These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1)date and time of all monitoring or sampling; (2)monitoring equipment calibration and maintenance records; <br /> (3)results of any visual observations; (4)results of sample analysis performed a lab or in the field; (5)logs of all <br /> readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6)results of <br /> inventory readings and reconciliations. <br /> CORRECTIVE ACTION: Immediately locate and maintain all missing maintenance and monitoring records for the last <br /> three years on site. Submit copies of any missing work orders and alarm records to the EHD. <br /> This is a repeat violation (Class 2) Violation. <br /> Overall TnPpe:tion RommentPd <br /> An inspection checklist was provided to the facility operator on the day of inspection. An amended complete <br /> report was finished on 6/12/2025 and replaces the initial checklist. <br /> FA0006672 PR0505264 SCO01 05/13/2025 <br /> EHD Rev.12/06/2021 Page 7 of 8 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 C 209 468-3420 1 N 209 464-0138 1 www.sjgov.org/EHD <br />