<br /> Underground Storage Tank Program Inspection Report
<br /> Facility Name: Facility Address: Date:
<br /> ARCO 06080 185 E LOUISE AVE LATHROP December 16 2025
<br /> 129 CCR 23 CCR 16 2635(a) 2030009-Cathodic protection is installed/maintained as required, including required ❑ OUT ❑ R ❑ COS
<br /> (2), 2636(b), 2662(c)(1) documentation (TCR 9c)
<br /> (B), 2712(b)(3)
<br /> 130 CCR 23 CCR 16 2643(b) 2030005-SW tank continuous in tank leak detection test is functioning properly ❑ OUT ❑ R ❑COS
<br /> (3) (TCR 9d)
<br /> 131 CCR 23 CCR 16 2643(b) 2030006-Monthly 0.2 gph ATG test is being conducted and copies of test results ❑OUT ❑ R ❑COS
<br /> (1) are available (TCR 9d)
<br /> 132 CCR 23 CCR 16 2641(e); 2060002-SW UST system has monitoring system capable of detecting releases ❑OUT ❑ R ❑COS
<br /> HSC 6.7 25292(a) (TCR 9d)
<br /> 133 CCR 23 CCR 16 2647, 2030022-Groundwater and/or vadose zone monitoring conducted,or site ❑ OUT ❑ R ❑ COS
<br /> 2648,2712(b)(4) assessment maintained (TCR 9d)
<br /> 134 CCR 23 CCR 16 2643(c) 2030052-.2 gph mthly or.1 gph yrly tests performed on piping, and .1 gph Win 30 ❑ OUT ❑ R ❑ COS
<br /> (2), 2643(c)(3), 2661(f); days of repair(TCR 9d)
<br /> HSC 6.7 25292(e)(2)
<br /> 135 CCR 23 CCR 16 2636(f) 2060012-LLD installed on pressurized piping system(TCR 9d) ❑ OUT ❑ R ❑ COS
<br /> (2), 2636(f)(5)(B), 2643(c)
<br /> (1), 2666(f); HSC 6.7
<br /> 25290.1(h), 25290.2(g),
<br /> 25291(f), 25292(e)
<br /> 136 CCR 23 CCR 16 2666(c), 2030027-LLD on SW press piping tests hrly, detects 3 gph leak, shuts down pump ❑ OUT ❑ R ❑ COS
<br /> 2643(c)(1) if leak or LLD fails(TCR 9d)
<br /> 137 CCR 23 CCR 16 2636(f) 2030025-LLD on DW press piping monitors hrly,detects a 3.0 gph leak, and ❑ OUT ❑ R ❑ COS
<br /> (2) restricts/shuts off flow(TCR 9d)
<br /> 138 CCR 23 CCR 16 2636(a) 2030053-SW Safe Suction piping drains back into storage tank,one check valve ❑ OUT ❑ R ❑ COS
<br /> (3), 2641(b) and inspections conducted
<br /> 139 HSC 6.7 25290.1(c)(3), 2030008-Secondary containment installed after July 1, 2003 is free of water ❑OUT ❑ R ❑COS
<br /> 25290.2(c)(3)
<br /> 140 CCR 23 CCR 16 2630(d), 2030040-Secondarily contained piping allows liquid to flow into the sump in the ❑OUT ❑ R ❑COS
<br /> 2641(a) event of a leak(TCR 9d)
<br /> 141 HSC 6.7 25290.1(c), 2030047-Secondary containment maintained tight and has been confirmed by ❑ OUT ❑ R ❑ COS
<br /> 25290.1(e), 25290.2(c), testing
<br /> 25291(a)(2)
<br /> 142 CCR 23 CCR 16 2635(b), 2060020-Spill buckets meet requirements, have been tested as required, and ❑ OUT ❑ R ❑ COS
<br /> 2637.1(a), 2637.1(b), records kept for 36 mths(TCR 9a)
<br /> 2637.1(c),2665(a),2665
<br /> (b), 2712(b)(1)(F); HSC
<br /> 6.7 25284.2
<br /> 143 HSC 6.7 25292.1(a) 2030035-UST system is operated to prevent unauthorized release, including spills ❑ OUT ❑ R ❑ COS
<br /> and overfills
<br /> 144 CCR 23 CCR 16 2635(c) 2030036-Overfill prevention system has not been overridden and meets overfill ❑ OUT ❑ R ❑ COS
<br /> (1), 2635(d), 2637.2(a) requirements(TCR 9b)
<br /> 2637.2(b), 2637.2(c),
<br /> 2665,2712(b)(1)(G)
<br /> 145 CCR 23 CCR 16 2711(a) 2010007-Submitted/maintained current Cert of Financial Responsibility/mech of ❑ OUT ❑ R ❑ COS
<br /> (11); HSC 6.7 25292.2(a) financial assurance(TCR 11)
<br /> 146 CCR 23 CCR 16 26310), 2030007-Documentation of compatibility for UST system components submitted ❑OUT ❑ R ❑ COS
<br /> 2631(1), 2631.1(b), and/or maintained.
<br /> 2640.1, 2665(b), 2666(b)
<br /> (2), 2666(e)(2), 2711(c),
<br /> 2712(b)(5)
<br /> 147 CCR 23 CCR 16 2716(f) 2010004-Copies of DO inspections for last 12 months maintained, 36 months for ❑ OUT ❑ R ❑ COS
<br /> those after 10/1/18(TCR 12)
<br /> 148 CCR 23 CCR 16 2716(a) 2030013-DO inspections completed at least every 30 days and meet all ❑OUT ❑ R ❑COS
<br /> through (e) requirements(TCR 12)
<br /> 149 CCR 2715(c), 2715(c)(1), 2030012-Initial and annual training provided to employees and at least one trained ❑OUT ❑ R ❑COS
<br /> 2715(c)(2) employee is present
<br /> EHD-CUPA Inspection Report IS03 Page 6 of 9 FA0003635 PR0231656 4589472 12/16/2025