Laserfiche WebLink
A dOAQU1N Environmental Health Department <br /> CQUNTY AMENDED <br /> 1/9/2025 <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: Facility Address: Date: <br /> TULARE FARMS LLLP 2771 E FRENCH CAMP RD, MANTECA January 06 2025 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> February 23, 2024, 5 days late. <br /> REGULATION GUIDANCE:A copy of the test report must be submitted within 30 days of the tests. <br /> CORRECTIVE ACTION: Take all necessary precautions to ensure testing and submittal of test reports are performed <br /> in a timely manner. <br /> This is a repeat violation (Class 2) Violation. <br /> 14 CA Code of Regulations 2637.2(d&e), 2665(a&b)2010018-Overfill prevention equipment inspection report form <br /> submitted to the UPA within 30 days. <br /> OBSERVATION:An overfill prevention equipment inspection was performed on January 19, 2024 and a test report was <br /> submitted on February 23, 2024, 5 days late. <br /> REGULATION GUIDANCE:A copy of the test report must be submitted within 30 days of the tests. <br /> CORRECTIVE ACTION: Take all necessary precautions to ensure testing and submittal of test reports are performed <br /> in a timely manner. <br /> This is a repeat violation (Class 2) Violation. <br /> 51 CA Health and Safety Code 25292.1(a)2030035- UST system is operated to prevent unauthorized release, including <br /> spills and overfills. <br /> OBSERVATION: Two deflector plates in the diesel dispenser and one deflector plate in the 87 dispenser were not <br /> positioned to redirect releases into the UDC. <br /> REGULATION GUIDANCE:The underground storage tank system shall be operated to prevent unauthorized releases, <br /> including spills and overfills. <br /> CORRECTIVE ACTION: This was corrected on site.The deflector plates were repositioned to appropriately redirect <br /> releases into the UDC. <br /> This is a repeat violation (Class 2) Violation. <br /> 85 CA Code of Regulations 2631(a); HSC 25290.1(c)2060027-Tank system primary containment is constructed, <br /> operated, and maintained product-tight.. <br /> OBSERVATION:Active leaks were observed in the diesel dispenser at the fuel filter, suction pump, and piping near the <br /> fuel filter indicating a leak in the primary containment. <br /> REGULATION GUIDANCE:All primary containment for the UST system must be product tight. <br /> CORRECTIVE ACTION: Immediately have a properly licensed, trained, and certified contractor repair or replace the <br /> failed components, under permit and inspection of the EHD if necessary. <br /> This is a repeat violation (Class 2) Violation. <br /> Overall Inspection Comments: <br /> FA0003508 PR0234251 SCO01 01/06/2025 <br /> EHD Rev.12/06/2021 Page 6 of 7 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />