Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST continued <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: <br /> Sump11,1113C ID UDC 112 UDC 314 UDC 516 UDC 718 <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 1:44 1:44 1:44 1:44 <br /> Initial Reading 4.3868 4.2821 5.7099 6.1180 <br /> Test End Time 1:59 1:59 1:59 1:69 <br /> Final Reading 4.3874 4.2822 5.7097 6.1181 <br /> Change in Reading 0.0006 , 0.0001 0.0002 0.0001 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail N Pass ❑ Fail <br /> Sump1UDC ID UDC 9110 UDC 11112 <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 3:03 3:03 <br /> Initial Reading 5.6768 4.1040 <br /> Test End Time 3:18 3:18 <br /> Final Reading 5.6767 4.1040 <br /> Change in Reading 0.0001 0 <br /> Pass/Fail Criteria 0.002 0.002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked�Fa#"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />