Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID UDC 9-10 UDC 11-12 <br /> Sump Manufacturer Unknown Unknown <br /> Sump Depth (inches) 30 30 <br /> Sump Bottom to Top of 9 9 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:55 AM 10:00 AM <br /> Initial Reading 0 0 <br /> Test End Time 10:25 AM 10:30 AM <br /> Final Reading 4.75" 4.75" <br /> Change in Reading 4.75" 4.75" <br /> Pass/Fail Criteria 0 0 <br /> Tightness Test Results ❑ Pass ® Fail ❑ Pass ® Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID 87 FILL 91 FILL DIESEL FILL <br /> Sump Manufacturer Unknown Unknown Unknown <br /> Sump Depth (inches) 60 60 60 <br /> Sump Bottom to Top of 0 0 0 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 12:30 PM 12:40 PM 12:50 PM <br /> Initial Reading 0 0 0 <br /> Test End Time 1:00 PM 1:10 PM 1:20 PM <br /> Final Reading 0 0 0 <br /> Change in Reading 0 0 0 <br /> Pass/Fail Criteria 0 0 0 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />