Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 9. COMMENTS <br /> Tank 87 STP Sump FAILED the hydrostatic test due to a bad test boot into the STP Sump. Boot <br /> must be replaced and 87 Sump retested with passing result. <br /> 87 Secondary Piping run FAILED the pressure test due to bad test boot into STP Sump. Boot must <br /> be replaced and 87 piping run re-tested with passing result. <br /> UDC #1-2, 3-4, 5-6, 7-8, 9-10, 11-12 FAILED the test due to bad penetration boots. Boots need to <br /> be replaced and UDC's retested with passing results. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 5 of 5 <br />