Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by ❑ Manufacturer 0 Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ED Hydrostatic <br /> Test Equipment Used: INCON TS-STS Tester <br /> Sump/UDC ID UDC 1/2 UDC 3/4 UDC 5/6 UDC 7/8 <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 12" 12" 12" 12" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration Bottom Bottom Bottom Bottom <br /> (inches) <br /> Test Start Time 12:45 pm 12:45 pm 12:45 pm 1:17 pm <br /> Initial Reading 1.7697 0.7761 1.0717 2.6253 <br /> Test End Time 1:00 pm 1:00 pm 1:00 pm 1:33 pm <br /> Final Reading 1.7698 0.7102 1.0717 2.6255 <br /> Change in Reading -0.0001 0.0659 0.0000 -0.0002 <br /> Pass/Fail Criteria 0.0020 0.0020 0.0020 0.0020 <br /> Tightness Test Results 0 Pass ❑ Fail ❑ Pass 0 Fail 0 Pass ❑ Fail 0 Pass ❑ Fail <br /> Sump/UDC ID UDC 9/10 UDC 11/12 <br /> Sump Manufacturer Bravo Bravo <br /> Sump Depth (inches) 122 12" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration Bottom Bottom <br /> (inches) <br /> Test Start Time 1:17 pm 1:17 pm <br /> Initial Reading 3.3405 2.7105 <br /> Test End Time 1:33 pm 1:33 pm <br /> Final Reading 3.3406 2.7114 <br /> Change in Reading -0.0001 -0.0009 <br /> Pass/Fail Criteria 0.0020 0.0020 <br /> Tightness Test Results El Pass ❑ Fail El Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />