SAN J0AQUIN <br />COUNTY <br />Environmental Health Department <br />Aboveground Petroleum Storage Act Program Inspection Report <br />Facility Name: <br />Facility Address: <br />12577 <br />Date: <br />CRST-EQUIPMENT SOLUTIONS <br />W YOSEMITE AVE MANTECA <br />June 19 2025 <br />10 <br />Code of Fed Regulations 112.5(b) 4010009 - 5 year review performed on SPCC and documented <br />OBSERVATION: The facility failed to perform the 5 -year review of the SPCC plan. The Spill Prevention, Control, and <br />Countermeasure (SPCC) Plan was last reviewed on 03/18/2019. <br />REGULATION GUIDANCE: (b) Notwithstanding compliance with paragraph [112.5] (a) of this section, complete a review <br />and evaluation of the SPCC Plan at least once every five years from the date your facility becomes subject to this part; <br />or, if your facility was in operation on or before August 16, 2002, five years from the date your last review was required <br />under this part. As a result of this review and evaluation, you must amend your SPCC Plan within six months of the <br />review to include more effective prevention and control technology if the technology has been field -proven at the time of <br />the review and will significantly reduce the likelihood of a discharge as described in § 112.1(b) from the facility. You must <br />implement any amendment as soon as possible, but not later than six months following preparation of any amendment. <br />You must document your completion of the review and evaluation, and must sign a statement as to whether you will <br />amend the Plan, either at the beginning or end of the Plan or in a log or an appendix to the Plan. The following words will <br />suffice, "I have completed review and evaluation of the SPCC Plan for (name of facility) on (date), and will (will not) <br />amend the Plan as a result." <br />CORRECTIVE ACTION: Immediately complete and document the 5 -year review of the SPCC Plan and make any <br />necessary amendments (a Professional Engineer must certify any technical amendments). Submit verification of <br />adequate SPCC plan review completion to the EHD. <br />This is a (Class 2) Violation. <br />32 <br />Code of Fed Regulations 112.7(f)(3) 4020002 - Spill prevention briefings are conducted annually <br />OBSERVATION: Failure to conduct spill prevention briefing for oil -handling personnel at least once a year to assure <br />adequate understanding of the SPCC Plan, including: <br />1. Known discharges or failures. <br />2. Malfunctioning components. <br />3. Any recently developed precautionary measures. <br />REGULATION GUIDANCE: (f)(3) Schedule and conduct discharge prevention briefings for your oil -handling personnel at <br />least once a year to assure adequate understanding of the SPCC Plan for that facility. Such briefings must highlight and <br />describe known discharges as described in § 112.1(b) or failures, malfunctioning components, and any recently <br />developed precautionary measures. <br />CORRECTIVE ACTION: Discharge prevention briefings for oil handling personnel must be scheduled and conducted at <br />least once a year to assure adequate understanding of the SPCC Plan for that facility. Conduct all required spill <br />prevention briefings. Provide compliance verification to the EHD. <br />This is a Repeat (Class 2) Violation. <br />55 <br />4030014 - Tanks inspected and tested by qualified person in accordance with industry standards <br />OBSERVATION: Facility failed to ensure that tanks are inspected and tested by an appropriately qualified person in <br />accordance with industry standards. The two 10,000 gallon double walled ASTs were not tested on schedule. The SPCC <br />plan stated that the tank integrity test was due in 2019. Paint flaking was observed on the surface of the two 10,000 <br />gallon ASTs. <br />REGULATION GUIDANCE: 112.8(c)(6) Test or inspect each aboveground container for integrity on a regular schedule <br />and whenever you make material repairs. <br />CORRECTIVE ACTION: Immediately ensure that all tanks are inspected and tested by an appropriately qualified person <br />in accordance with industry standards. Submit proof of correction/ test results to the EHD. <br />This is a Repeat (Class 2) Violation. <br />EHD - CUPA Inspection Report IS02 <br />Page 5 of 7 FA0010976 PR0513264 4518566 6/19/2025 <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />