Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. CONTAINMENT SUMP AND UDC TEST <br /> Test Method Developed by ❑ Manufacturer 0 Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used: iNCON Ts-sTs <br /> ❑ Check this box if Appendix 8.3 continuation page is attached. I <br /> Sump/UDC ID UDC 5/6 UDC 9/10 I <br /> Sump Manufacturer Bravo Bravo <br /> Sump Depth (inches) 101, 101, <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration o 0 <br /> inches <br /> Test Start Time 1:40 pm 1:40 pm <br /> Initial Reading 3.0360 1.2257 I <br /> Test End Time 1:55 pm 1:55 pm I <br /> Final Reading 3.0346 1.2256 <br /> Change in Reading 0.0014 0.0001 <br /> Pass/Fail Criteria 0.0020 0.0020 <br /> Tightness Test Results ❑✓ Pass❑Fail ❑✓ Pass❑ Fail ❑ Pass❑ Fail ❑ Pass❑Fail <br /> Continuity Test Results ❑ Pass❑Fail ❑ Pass❑ Fail ❑ Pass❑ Fail ❑ Pass❑Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> inches <br /> Test Start Time <br /> Initial Reading I <br /> Test End Time I <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass❑Fail ❑ Pass❑Fail ❑ Pass❑ Fail ❑ Pass❑Fail <br /> Continuity Test Results ❑ Pass❑Fail ❑ Pass❑Fail ❑ Pass❑ Fail ❑ Pass❑Fail <br /> Describe in Section 9 all tests marked "Fail"and any repairs made during the test. Page 3 of 4 <br />