Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. CONTAINMENT SUMP AND UDC TEST <br /> Test Method Developed by ❑ Manufacturer 0 Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used: Incon TS-STS Tester <br /> ❑ Check this box if Appendix 8.3 continuation page is attached. I <br /> Sump/UDC ID 87 STIR I <br /> Sump Manufacturer Fiberglass <br /> Sump Depth (inches) 64" <br /> Sump Bottom to Top of <br /> 21" <br /> Highest Pipe Penetration <br /> inches <br /> Test Start Time 1:37 pm <br /> Initial Reading 3.2783 I <br /> Test End Time 1:52 pm I <br /> Final Reading 3.2780 <br /> Change in Reading 0.0003 <br /> Pass/Fail Criteria 0.002 <br /> Tightness Test Results ❑✓ Pass❑Fail ❑ Pass❑ Fail ❑ Pass❑ Fail ❑ Pass❑Fail <br /> Continuity Test Results ❑ Pass❑Fail ❑ Pass❑ Fail ❑ Pass❑ Fail ❑ Pass❑Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> inches <br /> Test Start Time <br /> Initial Reading I <br /> Test End Time I <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass❑Fail ❑ Pass❑Fail ❑ Pass❑ Fail ❑ Pass❑Fail <br /> Continuity Test Results ❑ Pass❑Fail ❑ Pass❑Fail ❑ Pass❑ Fail ❑ Pass❑Fail <br /> Describe in Section 9 all tests marked "Fail"and any repairs made during the test. Page 3 of 4 <br />