Fire Safety Inspection, July 18, 2002: <br />Inside Storage Area — North 41): Portable and stationary tanks shall be stored inside gas <br />rooms or an enclosure with exhaust ventilation. CFC, 8002.2.1.2.1 <br />Sierra Chemical Response and Action: <br />SOP266/281 ST, Section 6.1: Handling — Chlorine and Sulfur Dioxide 150 Pound <br />Cylinder and Ton Container Handling and Storage. Storage of Cylinders and Ton <br />Containers — Full containers are to be stored in the Repack Room. <br />Cost: NA <br />Complaint (Code Reference 8003.3.1.3.5 vs. 8003.1.3.5.1): <br />13.1. Violation of CFC, Article 80, section 8003.3.1.3.5, failure to utilize the treatment system <br />to handle the accidental release of gas and process all exhaust ventilation to be discharged <br />from the gas room <br />Fire Safety Inspection, July 18, 2002: <br />Inside Storage Area — North 4E: Direct the exhaust ventilation to an exhaust system. <br />CFC, 8003.1.3.5.1 <br />Inside Storage Area — North 4F: The treatment system shall be utilized to handle the <br />accidental release of gas. The treatment system shall be utilized to process all exhaust <br />ventilation to be discharged from the gas room. CFC, 8003.3.1.3.5 <br />Sierra Chemical Response and Action: <br />No Violation - The chlorine repackaging room is equipped with an emergency chlorine <br />gas scrubber <br />Cost: NA <br />Complaint: <br />13.m. Violation of CFC, Article 80, section 8003.3.1.4, failure to provide emergency power in <br />lieu of stand-by power for (1) exhaust ventilation, including the power supply for <br />treatment systems, (2) gas detection systems, (3) emergency alarm systems, and (4) <br />temperature -control systems <br />Fire Safety Inspection, July 28, 2005: <br />Gas Room Item No. 1 — Emergency power shall be provided in lieu of standby power for: <br />a. Exhaust ventilation, including the power supply for treatment systems, b. Gas - <br />detection systems, c. Emergency alarm systems, and d. temperature -control systems. <br />CFC, Sec. 8003.3.1.4 (Emergency Power) <br />