Laserfiche WebLink
Tanknology <br />Emergency Stop (E -Stop / ESO) Periodic Inspection <br />Facility Information <br />Technician information <br />Site #: CHEVRON 307709 307709 <br />Date: 4/24/2013 <br />Address: 10858 TRINITY PKWY <br />Name: Jarrod Cooke <br />City / State: STOCKTON CA <br />Technician Signature: =� <br />The objective of this test is to provide assurance that the when the E -Stop switch is activated, all the fueling system circuits (turbines, and <br />dispensers) are de -energized, and remain de -energized until they are re -set manually). The test procedures and guidelines shall be in accordance <br />with the E -Stop Testing Process. <br />SITE DATA <br />1 <br />Number of E -Stop switches INSIDE of the building: <br />1 <br />2 <br />Number of E -Stop switches OUTSIDE of the building: <br />3 <br />PERFORMANCE DATA <br />Yes <br />Na <br />NA' <br />3 <br />You have added or confirmed that all E -Stop locations are on the Site Diagram <br />(: <br />r <br />r <br />4 <br />Do all E -Stops shutdown power to ALL DISPENSERS <br />is <br />(" <br />r <br />5 <br />Do all E -Stops shutdown power to ALL STP's <br />(. <br />r <br />6 <br />Are ALL E -Stops clearly Labeled <br />f+ <br />dam` <br />r <br />7 <br />Are the TURBINE BREAKERS clearly identified / labeled <br />POSTTEST <br />8 <br />All equipment secured and any access ports, lids, enclosures are closed. <br />(: <br />r <br />i <br />9 <br />All safety barricades and test equipment has been properly removed <br />(+ <br />r <br />10 <br />E -Stop was reset and all dispensing functions are normal <br />(. <br />(' <br />r <br />E -Stop Inspection Results <br />11 <br />PASS I FAIL I INCONCLUSIVE <br />Comments (Clearly describe any deficiencies found) <br />WO: 2310197 <br />