Laserfiche WebLink
SWRCB,January 2002 Page_ of <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: 0 Sump Manufacturer IJ Industry Standard X Professional Engineer <br /> 0 Other(Spec) <br /> Test Method Used: D Pressure 0 Vacuum X Hydrostatic <br /> 0 Other(Specie) <br /> Test Equipment Used Caldwell Level Change Indicator Equipment Resolution: .002MEN 111115 t! <br /> �I <br /> _- . - <br /> Sump# 1 Sump#2 Sump#3 Sump#4 <br /> Sump Diameter: 42" 42" 42" 42" <br /> Sump Depth: 73 %2" 731/2" 73 '/2" 75" <br /> Sump Material: Fiberglass Fiberglass Fiberglass Fiberglass <br /> Height from"Tank Top to Top of 2119 22" 19" 12" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 38" 29" 38" 29" <br /> Electrical Penetration: <br /> [-Condition of sump prior to testing:- Dry Dry Dry Dry <br /> Portion of Sump Tested' - �' Water Line 55" Water Line 55" Water Line 57" Water Line 52" <br /> Does turbine shut down when <br /> sump sensor detects liquid(both X Yes 0 No 0 NA X Yes GNo 0N X Yes 0N 0N X Yes No I:1 NA <br /> product and water)?' <br /> Turbine shutdown response time Not Alarmed Not Alarmed Not Alarmed Not Alarmed <br /> Is system programmed for fail-sale X Yes E No ]NA X Yes DNo GNA X Yes 0 No GNA X Yes Ci No [INA <br /> H shutdown?' <br /> -. - <br /> Was fail-safe verified to be Yes X No NA Yes X No l:a NA Yes X No GNA G Yes X No NA !! <br /> t... <br /> .-_.. <br /> operational?# <br /> j __... -...-.. -_ ...-.-.........._.- ......._...� <br /> Wait time between applying water 10 Minutes 10 Minutes 10 Minutes 10 Minutes <br /> and starting test: <br /> Test Start Time: i 11:20 11:30 11:55 12:50 <br /> Initial Reading(Rr): _ .001 .001 .001 _ .001 ^ _- <br /> Test End Time: - 11:50 12:00 12:25 1:20 <br /> Final Reading(RF): .001 .001 .001 .001 <br /> i Test Duration: 30 Minutes 30 Minutes 30 Minutes 30 MinutesI <br /> Change in Reading(RF-Ri): 0 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005/30 Minutes .005/30 Minutes .005/30 Minutes <br /> _....-.._. ....... _ -..�.._.. <br /> Test Result: L X Pass ❑Fail X Pass Q Fail X Pass ❑Fall X Pass ❑ Fail <br /> Was sensor removed for testing? LX Yes ]No ❑NA X Yes No 0 NA X Yes O No GNA X Yes G No D NA <br /> Was sensor properly replaced and X Yes 0 No C NA X Yes DNo 0N X Yes 0N 0N X Yes LlNo PI NA <br /> verified functional after testing? xNpj <br /> Comments- (include information on repairs made prior to testiand reco»rmended follow-ups for failed tests) <br /> If the entire depth of the sump is not tested,specify how much was tested. If the answer to a y of the questions indicated with an <br /> asterisk(*) is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />