Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: 0 Sump Manufacturer 0 Industry Standard X Professional Engineer <br /> 0 Other(Spec) l! <br /> Test Method Used: 0 Pressure 0 Vacuum X Hydrostatic — <br /> 0 Other(Spec) <br /> I Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> _ _ <br /> Sump#5 Sump#6 Sump#7 Sump#8 <br /> Sump Diameter: 42" 4211 42" 42" <br /> i Sump Depth: 75" 74'/x" 74 %z" 74" <br /> Sump Material: Fiberglass Fiberglass Fiberglass Fiberglass <br /> Height from Tank"Top to Top of No Piping No Piping No Piping No Piping <br /> Hi hest Pi in Penetration: Penetrations Penetrations Penetrations Penetrations <br /> Height from Tank Top to Lowest 42" 42" 42" 30" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Dry Dry Dry Dry <br /> Portion of Sump Tested' Water Line 44" Water Line 44" Water Line 44" Water Line 44" <br /> Does turbine shut down when I' <br /> suntp sensor detects liquid(both Yes X No ❑NA Yes X No DNA X Yes 0 No 0 NA ,0 Yes X No C::;NA <br /> _product and water)?` <br /> Turbine shutdown response time NIA N/A N/A NIA <br /> Is system programmed for fail-safe X Yes L No DNA X Yes rL'No DNA X Yes 0N DNA X Yes 0N iDNA <br /> i shutdown?* <br /> Was fail-safe verified to be <br /> Yes X No ❑NA Yes X No DNA Yes X No DNA 0 Yes X No —­NA <br /> operational?' — <br /> Wait time between applying water i <br /> and starting test: 5 Minutes 5 Minutes 5 Minutes 5 Minutes <br /> Test Start Time: 12:05 12:10 12:15 12.55 <br /> .001 .001 .001 .001 <br /> Initial Reading(R,): ................ii <br /> Test End Time: 12:35 12:40 12:45 1:25 � <br /> Final Reading(RF): .001 .001 .001 .001 <br /> --.. <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> t Change in Reading(RF-Ri): 0 0 0 0 j <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005/30 Minutes .005/30 Minutes .005/30 Minutes <br /> Test Result: X Pass 0 Fail X Pass 0 Fail X Pass 0 Fail X Pass 0 Fail <br /> Was sensor removed for testing? X Yes 0 No NA X Yes D No 0 NA X Yes 0 No [INA X Yes 0 No ENA <br /> Was sensor properly replacedand X Yes 0 No i l NA X Yes DNo ONA X Yes ONo 0N X Yes 0N i.Wi NA <br /> verified functional afttesting <br /> er <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Piping Sump#5 is for Annular Riser and Tank Probe Riser for Tatik#I Diesel. <br /> Piping Sump 46 is for Annular Riser and Tank Probe Riser for Tank#2 Diesel. <br /> Piping Sump#7 is for Annular Riser and Tank Probe Riser for Tank#3 Regular. <br /> Piping Sump#8 is for Annular Riser and Tank Probe Riser for Tank#4 Regular. <br /> If the entire depth of the sump is not tested,specify how much was tested. If the answer to ggy of the questions indicated with an <br /> asterisk(*) is"NO"or"NA", the entire sump must be tested. (See SWRCB LG-160) <br />