Laserfiche WebLink
SWRCE,January 2442 Page 4 of 7 <br /> 6. PIPING SttW TESTING <br /> Test Nletbod Developed By 0 Sump Manufacturer X Industry Standard ❑Professianal Engineer <br /> ❑Other(Specrhl <br /> Fest Mcthod Used: 0 Pressure 0 Vacuum X Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Tncon TS STS Equipment Resolution: <br /> Sump#regular Sump#premium Sump# SUMp# <br /> Sump Diameter: 42" 42" <br /> Sump Depth: 4r 4V <br /> Sump Material: Fiberglam iFibergiass <br /> Height from Tank Top to Top of 14" 15' <br /> Hi est P!Rju Penetration: <br /> Height from Tank Top to Lowest <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Clean Clean <br /> Portion of Sump Tested' Pull Full <br /> Does tuzhine shut down when <br /> sump sensor detects liquid(both XYes ❑No 0 NA XYes ❑No 0 NA ❑Yes ❑No 0 NA 0 Yes 0 No [INA <br /> product and water)? <br /> Turbine shutdown,response time 2 Seconds 2 Seco�ads <br /> Is system programmed for fail-safe <br /> shutdown?* XYes 0 No ❑NA XYes ❑No ❑NA 0 Yes n No l]NA 0 Yes ❑No ❑NA <br /> _ <br /> Was fail-safe verified to be XYes 0 N 71-NA XYes 0 N 0 N ❑Ycs DNo DNA 1_1Yes rsNo [INA <br /> o ioual?' <br /> Wait time between applying <br /> presswe/vacuumfwater and starting 10 Minutes 10 Minutes <br /> test: <br /> Test Start Time- 1.2:1$pm 12:18 pm <br /> Initial Reading(RT):. 5.0179" 801406" <br /> Test End-.Circe: 12.33 pm 12:33 pm <br /> Final leading(RF): 5.4173" 0.1401" <br /> Test Duration: 15 Minutes 15 minutes <br /> Change in Reading(R,,RT): .0006" .04RS" <br /> Pass/Fail Threshold or Criteria: -,402"=pass <002"=pass <br /> 'Fest Result; X Pass 0 Fail X Fags 0'Fail 0 Pass 0 Fail C1 Fass 0 Fail <br /> Was sensor removed for testing? XYes 0 No ❑NA. XYes 0 No ❑NA 0 Yes ❑No ❑NA 0 Yes ❑No DNA <br /> Was sensor properly roplared and XYes ❑No 0 NA XYes ❑No DNA ❑Yes ❑No ❑NA ❑Yes C No 11 NA <br /> verified f metional after testi n1 11 <br /> COMWO s— (include irj�rmadon on repairs mode prior to testi and recommended fbfloww-upfLrA!a Ied tests <br /> If the entire depth of the sump is not tested,specify how much was tested. Tf the answer to M of the questions itndi:tated with an <br /> asterisk(*)is"NO"or"N.A-,the entire sump must be tested. (See$WRCB LG-160) <br />