Laserfiche WebLink
l GEIVE <br /> SWRCB, January 2002 MAR 2 7 2015 <br /> Page_of <br /> 7 .PIPING SUMP TESTING ! ":NVIRONMENTAi <br /> Test Method Developed By: L Sump Manufacturer L Industry Standard X Prof$ss!641 Engineer <br /> L Other(Spec) <br /> Test Method Used: Pressure L Vacuum X Hydrostatic <br /> Other(Specify) <br /> Test Equipment Uscd Caldv�ell I ecel Chin e Indicator Equipment Resolution: .002 <br /> _ <br /> Sump# I <br /> Sump Diamcici - 42„ P Sump#2 Sump#3 Sump#4 <br /> 42" 42" 42„ <br /> Sump Depth: 39" 42" 44" 39" <br /> Sump Material: Fiberglass Fiberglass Fiberglass Fiberglass <br /> Height from Tank Top to Top of 26" <br /> Highest Piping Penetration: 36" 38" 21" <br /> Height from Tank Top to Lowest <br /> Electrical Penetration: 24 21" 38" 23" <br /> Condition of sump prior to testing: Dry Dry Dry Dry <br /> Portion of Sump Tested' Water Level 28" Water Level 38" Water Level 40" Water Level 28" <br /> Does turbine shut down when <br /> sump sensor detects liquid(both Yes Yes Yes Yes <br /> roduct and water <br /> )?. <br /> Turbine shutdown response time Not Alarmed Not Alarmed Not Alarmed Not Alarmed <br /> Is system programmed for fail-safe <br /> shutdown?* Yes Yes Yes Yes <br /> Was fail-safe verified to be <br /> o erational?* No No No No <br /> Wait time between applying water <br /> and starting test: 5 Minutes 5 Minutes 5 Minutes 5 Minutes <br /> Test Start Time: 9:35 9:30 12:05 12:55 <br /> Initial Reading(R,): .001 .001 .001 .001 <br /> Test End Time: 10:05 1000 12:35 1;25 <br /> Final Reading(Rr): .001 .001 .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading(RF-R,): 0 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005/30 Minutes .005/30 Minutes .005/30 Minutes <br /> Test Result: Pass Pass Pass Pass <br /> Was sensor removed for testing? Yes Yes Yes Yes <br /> Was sensor properly replaced and <br /> verified functional after testin ? Yes Yes Yes Yes <br /> Comments—(include information on repairs made prior to testing and recommended follow-up orfailed tests) <br /> If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />