Laserfiche WebLink
a <br /> 1 Ih Al y <br /> Dispenser Interface Module(DIM) "1�: 1 r(�-1W006T <br /> 1. Verify that DIM Installation kit corresponds with onsite Dispenser and POS equipment compatibility. <br /> 2. Printout and Archive Setup configuration <br /> 3. Verify Communication Slot is available - - <br /> 4. If Communication Slot is available, remove power from TLS. <br /> 5. Install DIM and appropriate Installation cables per the Dispenser Interface installation manual, 577013- <br /> 614 that Is provided with DIM. <br /> Remote— v— er—ificaflon <br /> 1. When work is completed, call FMS at 1-800-997-7725 option 4, option 1 (avallable 24 hours) <br /> 2. Inform FMS agent that you have lust completed a Costco BIR Upgrade and that the FMS agent should <br /> have some Instructions to follow. <br /> 3. The FMS agent will run a startup which will verify remote dial out programming and Import current site <br /> setup. <br /> 4. After the startup Is completed the FMS agent will program the TLS to dialoutto verify that outbound - <br /> communications is successful. <br /> 5. The FMS agent will then compare the previous setup of the site to the current programming of the site. <br /> Any setup parameters that do not match the site previous setup will be discussed with you as to why <br /> they do not match and what action should be taken. <br /> 6. If the setup parameters match Identically this process should not take any more than 10 or 15 minutes. <br /> If multiple parameters need to be discussed the time will be extended. Please make sure TLS <br /> programming matches the original as best as possible prior to calling FMS. <br /> Gotcha's to watch out for <br /> The current released software version does not allow sites with older 333.xx software to have <br /> Maximum-volume-set-above-the-Full-Volume, reference.-chart.below.--For-example-if-Full-Volume.is.set-at-19949 <br /> and Max Volume is set at 19951, the Setup Data Warning will appear which will not clear on Its own, until it is <br /> corrected. This is considered a safety feature, The Overfill and High Product Alarm thresholds regarding <br /> percentages are based off of the Max Volume entry. For Installs that encounter this type of alarm, the Max <br /> Volume needs to be changed to match the Full Volume <br /> -TANK 20 POINT FULL VOLUMES - - -. <br /> TANK PRODUCT LABEL GALLONS <br /> 1 Unleaded 19949 19827 19327 18607 <br /> 2 Unleaded 19949 19767 19225 18477 <br /> 3 Premium 19867 19710 19187 18453 <br /> 4 Additive 1514 0 0 0 <br /> TANK MAXIMUM VOLUME LIMIT <br /> I <br /> TANK PRODUCT LABEL GALLONS <br /> 1 Unleaded 18951 <br /> 2 Unleaded 19951 <br /> 3 Premium 19951 <br /> 4 Additive ..1514' j <br /> Veeder-Root Technical Support Contact lnformatlon - <br /> 1-800-323-1799 <br />