Laserfiche WebLink
6, PIPING SUMP TESTING <br /> Test Method Developed By: ❑ Sump Manufacturer ® industry Standard ❑Professional Engineer <br /> ❑other(Specify) _ <br /> I est Method Used: ❑ Pressure LJVacuum E Hydrostatic <br /> ❑other(Specify) <br /> Test Equipment Used: [NCON TS-STS Equipment Resolution: 0.000 <br /> BANINIGNE <br /> Sump#87 Sump#89 Sump#91 Sump# <br /> Sump Diameter: 46" 46" 46" <br /> Sump Depth: 45" 55" <br /> Sump Material: FG FG FG <br /> Height from Tank Top to Top of 33" 23" 23" <br /> Highest Piping Penetration: <br /> Height from Tank'1'op to Lowest 301, 25" 16" <br /> Electrical Penetration: <br /> Condition ofsampprior totesting: _ FAIR FAIR FAIR <br /> Portion of Sump Tested' 40" 36" 30" _ <br /> Does ttubine shut down when <br /> sump sensor detects liquid(both E Yes❑No❑NA E Yes❑No❑NA E Yes❑No❑NA ❑Yes❑No❑NA <br /> product and water)?* <br /> Turbine shutdown response time t0 SEC I O SEC 10 SEC <br /> Is system programmed for fail-safe E Yes❑No❑NA E Yes❑No❑NA E Yes❑No❑NA ❑Yes❑No❑NA <br /> shutdown'?" �.-.._.__ <br /> Was fail-safe verified to be E Yes❑No❑NA E Yes❑No❑NA E Yes❑No❑NA ❑Yes❑No❑NA <br /> operational?' <br /> Wait time between applying T <br /> pressure/vacuum/water and starting 15 MIN 15 MIN 15 MIN <br /> test: <br /> Test Start Time: 1:11 1:11 1:58 <br /> Initial Reading(Rt);_.__..._._—. 2.8189 5.6244 4.7253 <br /> Test End Time: 1:26 1:26 2:13 <br /> Final Reading(Rr): 2.8189 5.6244 4.7257 <br /> `I est Duration: 15 MIN 15 MIN 15 MIN <br /> Change in Reading(Rt-Rh): 0.0000 _ 0.0000 0.0004 <br /> PassiFail Threshold or Criteria: 0.002 0.002 0.002 <br /> Test Result: : ®Pass ❑ Fail ®Pass ©Fail_T E_Pass ❑Fail ❑_Pass.: ❑ Fail <br /> Was sensor removed for testing? E Yes❑No NA E Yes❑No❑NA [I Yes❑No❑NA ❑Yes❑No❑NA <br /> Was sensor properly replaced and E tires❑No❑NA E Yes❑No❑NA E Yes❑No❑NA ❑ Yes❑No❑NA <br /> verified functional after testing? <br /> Comments— (include in/brmation on repairs made prior to testing and recommended follow-up fir failed tests) <br /> RECEIVED <br /> NOV 2 5 1014 <br /> ENVIRONMENTAL <br /> ' if the entre depth of the sump is not tested;Specify how much was tested. If the answer to my of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See S WRCB LG-160) <br /> Secondary Containment Test Results 4 of 6 <br />