S WRCB, January 2002 • <br />6. PIPING SUMP TESTING <br />• Page '_ of_ <br />Test Method Developed By: D Sump Manufacturer D Industry Standard X Professional Engineer <br />D Other (Spec) <br />Test Method Used: D Pressure D Vacuum X Hydrostatic <br />D Other (Spec) <br />Test Equipment Used: Caldwell Level Change Indicator <br />Sump # 1 Sump # 2 <br />Equipment Resolution: .002 <br />Sump # 3 <br />Sump # <br />Sump Diameter: <br />42" <br />42" <br />42" <br />Sump Depth: <br />51" <br />52" <br />53" <br />Sump Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />product 13" <br />Product 13" <br />Product 15" <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />9'/," <br />12" <br />13'/:" <br />Condition of sump prior to testing: <br />Dry <br />Dry <br />Dry <br />Portion of Sump Tested' <br />Water Level 15" <br />Water Level 14" <br />Water Level 18" <br />Does turbine shut down when <br />sump sensor detects liquid (both <br />product and water)? <br />X Yes D No D NA <br />XYes DNo DNA <br />X Yes D No D NA <br />Turbine shutdown response time <br />Not Alarmed <br />Not Alarmed <br />Not Alarmed <br />Is system programmed for fail-safe <br />shutdown? <br />X Yes D No DNA <br />XYes DNo DNA <br />XYes DNo DNA <br />Was fail-safe verified to be <br />operational?* <br />Yes X No DNA <br />Yes X No DNA <br />Yes X No D NA <br />Wait time between applying water <br />and starting test: <br />5 Minutes <br />5 Minutes <br />5 Minutes <br />Test Start Time: <br />9:10 <br />8:30 <br />9:20 <br />Initial Reading (111): <br />.001 <br />.001 <br />.001 <br />Test End Time: <br />9:40 <br />9:00 <br />9:50 <br />Final Reading (RF): <br />.001 <br />.001 <br />.001 <br />Test Duration: <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />Change in Reading (RF -R,): <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30 Minutes <br />.005/30 Minutes <br />.005/30Minutes <br />Test Result. , <br />X Pass D Fail <br />X Pass D Fail <br />X Pass ❑Fail <br />Pass .`D Fail <br />Was sensor removed for testing? <br />X Yes D No D NA <br />Yes D No 0 NA <br />X Yes D No D NA <br />Yes D No D NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />X Yes D No D NA <br />Yes D No D NA <br />XYes DNo DNA <br />Yes D No D NA <br />Comments — (include information on repairs made prior to testing and recommended ollow-up for failed tests) <br />"the entire depth of the sump is not tested, specify how much was tested. If the answer to amny of the questions indicated with an <br />. nerisk (*)is "NO" or "NA", the entire sump must be tested. (See SWRCB LG -160) <br />