Laserfiche WebLink
SWRCB,January 2002 • <br />• <br />7. UNDER -DISPENSER C.ONTAINMF.NT rttnr l TFaTnvn <br />Page _ of_ <br />Test Method Developed By: D UDC Manufacturer D Industry Standard X Professional Engineer <br />D Other (Spec) <br />Test Method Used: D Pressure D Vacuum X Hydrostatic <br />D Other (Spec) <br />Test Equipment Used: Caldwell Level Change Indicator <br />UDC # 1&2 -RT UDC # 3&4 -RT <br />UDC Manufacturer: Bravo Bravo <br />Equipment Resolution:.002 <br />UDC # 5&6 -RT UDC # 7&8 -RT <br />Bravo <br />Bravo <br />UDC Material: <br />Coated Steel <br />Coated Steel <br />Coated Steel <br />Coated Steel <br />UDC Depth: <br />10" <br />10" <br />10" <br />10" <br />Height from UDC Bottom to Top <br />of Highest Piping Penetration: <br />See Comments <br />See Comments <br />See Comments <br />See Comments <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: _ <br />See Comments <br />See Comments <br />See Comments <br />See Comments <br />Condition of UDC prior to <br />testing: <br />Dr, <br />Dry <br />Dry <br />Dry <br />Portion of UDC Tested <br />Water Level 8" <br />Water Level 8" <br />Water Level 8" <br />Water Level 8" <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />product and water)? <br />Yes X No D NA <br />Yes X No D NA <br />Yes X No D NA <br />Yes X No D NA <br />Turbine shutdown response time <br />N/A <br />N/A <br />N/A <br />N/A <br />Is system programmed for fail- <br />safe shutdown?* <br />X Yes D No D NA <br />X Yes D No D NA <br />X Yes D No D NA <br />X Yes D No D NA <br />Was fail-safe verified to be <br />operational? . <br />Dyes X No DNA <br />—T—Minutes <br />D Yes X No DNA <br />D Yes X No DNA <br />D Yes X No D NA <br />Wait time between applying <br />water and starting test <br />5 Minutes <br />5 Minutes <br />5 Minutes <br />Test Start Time: <br />11:30 <br />11:35 <br />11:40 <br />11:50 <br />Initial Reading 111): <br />.001 <br />.001 1 <br />.001 <br />.001 <br />Test End Time: <br />12:00 <br />12:05 <br />12:10 <br />12:20 <br />Final Reading(RF): <br />001 <br />.001 <br />.001 <br />.001 <br />Test Duration: <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />Change in Reading RF -R,: <br />0 <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005130 Minutes <br />.005/30 Minutes <br />.005/30 Minutes I <br />005/30 Minutes <br />Test Result. t"I 3i} , <br />a' s ,I Fail <br />XYes DNo DNA <br />dEal <br />XYes DNo DNA <br />pas `; .lgfkatl I <br />XYes DNo ❑NA 1XYcs <br />XSC P.as9 % '{7 Fail <br />DNo DNA <br />Was sensor removed for testing? <br />Was sensorfunctional after testing? properly replaced and <br />verified <br />X Yes D No D NA <br />X Yes D No D NA <br />X Yes D No D NA <br />X Yes DNo DNA <br />Comments — (include information on repairs made prior to testing. and recommended fnllnw-un fnr failed to cm) <br />All Penetrations enter from of Bravo System UDC's. <br />RT=Retail Island. <br />If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />terisk (*)is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />